PORTABLE APPLIANCE TESTER

KEW6205

INSTRUCTION MANUAL

Содержание KEW6205

Страница 1: ...PORTABLE APPLIANCE TESTER KEW6205 INSTRUCTION MANUAL...

Страница 2: ......

Страница 3: ...ment 18 4 1 Visual inspection 18 4 2 Battery Voltage Check 18 4 3 Setting 18 4 3 1 Null setting 18 4 3 2 Voltage setting for insulation resistance measurement How to change between 250V and 500V 19 5...

Страница 4: ...rocedures It is essential to read and to understand the safety rules contained in these instructions and with the safety procedures The symbol indicated on the Tester means that the user must refer to...

Страница 5: ...spection and repair Never attempt to use the Tester if the Tester or your hands are wet Stop using the test lead if the outer jacket is damaged and the inner white jacket is exposed CAUTION When using...

Страница 6: ...ater momentary energy than one designed for CAT II O Circuits which are not directly connected to the mains power supply CAT II Electrical circuits of equipment connected to an AC electrical outlet by...

Страница 7: ...additional insulation where any metal parts cannot become Live under fault conditions 2 2 Test Function CL I Protective conductor resistance test Test current 200mA DC nominal Insulation test 250V or...

Страница 8: ...tinuity test 1 sec Long press Starts CLI test Continuity test 5 sec CLII switch Starts CLII test Extension switch Short press Starts Extension lead test Continuity test 1 sec Long press Starts Extensi...

Страница 9: ...and 500 V Default setting 250 V Light switch Short press Turns on off LCD backlight Long press Enters into clock mode RCD switch Switches to RCD stand by screen Another press on the stand by screen s...

Страница 10: ...been set Rated voltage for insulation resistance test Leakage current test under actual working condition Rated current for RCD test Measurement in progress Protective conductor resistance Insulation...

Страница 11: ...polarity test Crossed L N polarity warning resistance between L N N L is 10 or lower at polarity test Short circuited L N warning resistance between L N is 100 k or lower at insulation test Extension...

Страница 12: ...A to this terminal for the measurement of protective conductor resistance and clip the metal parts of DUT with the alligator clip 4 Terminal for Extension leads adaptor It corresponds to L N E of test...

Страница 13: ...t according to a measurement use 1 Protective nger guard is a part providing protection against electrical shock and ensuring the minimum required air and creepage distances 3 Extension leads adaptor...

Страница 14: ...13 2 6 Optional accessories 1 Printer cable MODEL7275 2 USB cable with KEW Report Software MODEL8263 USB...

Страница 15: ...Measuring range 0 00 20 00 NULL value included Over range indication 21 00 Resolution 0 01 Open circuit voltage 5 V 0 4 V DC Measuring current 200 mA DC nominal value Accuracy 3 rdg 5dgt Resistances e...

Страница 16: ...g 5dgt Max rating 2 5 kVA max 15 sec continuous Insulation test between L N at Extension Lead Test Open circuit voltage 4 5 V 0 5 V DC Criteria of judgement 100 k 20 k or less LCD shows 0 10 M and the...

Страница 17: ...230 V 15 10 Rated frequency 50 Hz Maximum load current at test socket 2 5 kVA 15sec Outer dimension and weight Outer dimension 261 L 104 W 57 D mm Weight including batteries Approx 940g Auto power of...

Страница 18: ...testing without tripping the RCD of mains power Crossed out wheel bin symbol according to WEEE Directive 2002 96 EC indicating that this electrical product may not be treated as household waste but t...

Страница 19: ...ry recommendation Use of alkaline battery is recommended Use of other type of batteries may cause improper indication of battery level 4 3 Setting 4 3 1 Null setting AS NZS3760 pass level for Protecti...

Страница 20: ...leared and a new value is saved When 3 or higher is measured previous NULL value is just cleared NULL mark disappears 4 3 2 Voltage setting for insulation resistance measurement How to change between...

Страница 21: ...pliance to the test socket 1 described in clause 2 4 3 Connector and the Rpe Test Lead terminal 3 To perform RUN leak test connect Mains lead MODEL7277 to Mains lead terminal 2 1 Continuity test Earth...

Страница 22: ...stance test 1 Continuity test DUT is ON DUT is OFF Voltage value is displayed while the Tester is connected to an outlet Press to halt a measurement in progress DUT is powered on or CL I is pressed In...

Страница 23: ...Check screen for RUN leakage test Buzzer sounds and blue backlight blinks RUN Leak Load current test Red backlight blinks CL Rins 1M PASS Rins 1M FAIL ILEAK 5mA PASS Green backlight blinks ILEAK 5mA...

Страница 24: ...d the Tester cannot continue the test automatically In such a case press CL I switch to continue the test Follow the procedure described in 4 3 1 and undertake the NULL setting before a measurement Th...

Страница 25: ...ge current test RUN Leak test Connect Tester to outlet Load current is also measured Connect to exposed metal parts but not rotating parts or heating elements Switch ON the power Press CLII switch to...

Страница 26: ...is ON DUT ON Check Insulation resistance test DUT is powered on or CL II is pressed Press to halt a measurement in progress Tester performs next test when CL II switch is pressed while a test is halte...

Страница 27: ...Check screen for RUN leakage test Buzzer sounds and blue backlight blinks RUN Leak Load current test Red backlight blinks Red backlight blinks Green backlight blinks CL Rins 1 M PASS Rins 1 M FAIL ILE...

Страница 28: ...while testing is in progress Since a high voltage of 250V or 500V will be present and the user may get an electrical shock WARNING When conducting a leakage test the appliance will automatically power...

Страница 29: ...olarity check of the Line and Neutral terminal of plug and socket Run leakage current test Run leakage current test on Extension Leads Test doesn t measure load current 1 Continuity test For PE termin...

Страница 30: ...st Insulation resistance test between 1 L N E 2 L N Press to halt a measurement in progress Tester performs next switch is pressed while a test is halted with FAIL indication Red backlight blinks Red...

Страница 31: ...L and N is reversed Cross Break in L or N Open Check screen for RUN leakage test Buzzer sounds and blue backlight blinks RUN Leak test 4 Leakage current test Red backlight blinks Red backlight blinks...

Страница 32: ...ng the MODEL 7276 into the Extension Lead Adaptor terminal and the AU socket on the front of the unit When the terminal is open or the resistance value exceeds the measuring range over range display a...

Страница 33: ...ed Tripping Current I n of 10 mA or 30 mA PRCD trip time is measured in sequence 1 0 1 180 5 0 5 180 After each test reset the tripped PRCD to proceed to the next test PASS result is given where the P...

Страница 34: ...RCD Test Flow 30mA 10mA Stand by Long press switches I n 10 mA and 30 mA RCD test stand by screen 1 0 test 1 0 test result Reset the tripped RCD Press to halt a measurement in progress 1sec RCD RCD R...

Страница 35: ...esult Reset the tripped RCD 5 0 test 5 0 test result Reset the tripped RCD 5 180 test Test results are all PASS If any one of test results is FAIL FAIL is displayed PASS is displayed Red backlight bli...

Страница 36: ...indicates when testing a PRCD connected to a socket outlet For this test use MODEL7276 for connection If a fault voltage exceeds 50 V while applying a test current to test a built in type RCD the LCD...

Страница 37: ...n MEMORY Short press 2 Data No edit screen PRINT Enter POWER ESC 1 Site No edit screen Device No edit screen PRINT Enter PRINT Enter POWER ESC POWER ESC PRINT Enter Blink Blink Blink Blink Blink 1 All...

Страница 38: ...aved data can be recalled according to the following sequence On any screen RECALL POWER ESC Data No and result are displayed The latest saved data is displayed Saved date site no and device no are di...

Страница 39: ...ete just one result or all results Data can be deleted according to the following sequence On any screen RECALL POWER ESC The latest saved data is displayed POWER ESC RECALL MEMORY Simultaneous press...

Страница 40: ...le MODEL7275 to connect a printer and the instrument Long press of the PRINT switch can toggle and change the site no or device no for print Compatible printer TLP2824PLUS Zebra The table below shows...

Страница 41: ...ESC PRINT Long press Site No edit screen Device No edit screen PRINT Enter PRINT Enter The displayed device no stops blinking Data output to printer Returns to the first screen Blink Blink Site No Dev...

Страница 42: ...ble MODEL8263 to connect the instrument and a PC The table below shows the USB communication specs Help and information on how to install KEW Report please see the instruction manual supplied with MOD...

Страница 43: ...according to the following sequence On any screen POWER ESC LIGHT Long press Show the current date and time POWER ESC PRINT ENTER PRINT ENTER Edit mode Date RCD RCD RCD RCD RCD Edit mode Month Edit mo...

Страница 44: ...ssible electric shock remove test leads before opening the battery cover After replacing batteries be sure to tighten up the screws for battery cover CAUTION Do not mix new and old batteries Install b...

Страница 45: ...eplace the fuse Fuse type 10A 250V F Fast acting type ceramic fuse 5 x 20mm 3 Screw the battery cover back on before using the Tester 12 Shoulder strap attachment 1 Turn the knob counterclockwise unti...

Страница 46: ...Pass the strap belt down through the buckle from the top and up Adjust the strap for length and secure 13 Maintenance Use a very slightly damp cloth for cleaning the Tester Do not use abrasives or sol...

Страница 47: ......