Digital UnderVoltage Relay (GDR-D01) User's Manual V1.10
16 / 47
Kyongbo Electronics Co., Ltd.
3.
Protection Characteristics
3.1 UnderVoltage Function
This relay contains the Inverse Time characteristic and Definite Time characteristic
to be used for UnderVoltage protection. OP MODE can be set to DIGITAL and
INDUCTION mode. When it is set to DIGITAL, the Undervoltage element does
not operate when the initial power is supplied to the relay or after Reset recovery,
and it only operates when the voltage goes above the setting value and drops under
the setting value. When it is set to INDUCTION, it maintains the induction type
relay operation characteristic, so the existing induction type relays are generally
acceptable. Several recovery functions are included in the state operated by
UnderVoltage element, the recovery function for the voltage going above the setting
value, the recovery function when Reset Key is pressed when the operation mode is
set to Digital, and the recovery function after the recovery time(RST-Time) when
recovery function(RST-Mode) is ON.
NI characteristic is function of time therefore operating time is short as large voltage.
×
sec
T = Operation Time
V = Relay input voltage / Relay operation setting value
M = Operation time ratio
The time and voltage relationship function is as follows.
【
Figure 3.1
】
UVR Logic Diagram