Digital Overcurrent & Ground Overvoltage & Selective Ground Relay (GDR-AEF01) User's Manual
38 / 67
Kyongbo Electronics Co., Ltd.
- 〉
P o w e
r
S y s
t
e m
1
.
F R E Q
:
6 0 H z
*
2
.
G _ P T _ R A T :
1
.
0
:
1
3
.
P _ C T _ R A T :
5
:
5
Press
Key in Power system screen, then it will exit this menu and convert to the
upper menu.
Ÿ
System Config.
▶
Power system
▶
FREQ Setting
It is a category to set the common frequency used in the system where the relay
is used.
There are two categories, 50Hz and 60Hz, and for cable using 60Hz, select 60Hz.
Ÿ
System Config.
▶
Power system
▶
G_PT_RAT Setting
It is a category to set the 1st voltage ratio on Phase side. It can be set in 0.1
units from 0.1 to 3200.0. For example, if using voltage of ground side as
6600:190, set 34.7 in G_PT_RAT setting.
Ÿ
System Config.
▶
Power system
▶
P_CT_RAT Setting
It is a category to set the 1st CT ratio on Phase side. It can be set in 5 units
from 5 to 10000. This relay is designed for CT 2nd rated to be 5A, so CT with
5A 2nd must be selected when selecting CT. For example, if using CT of Phase
side as 1000:5, set 1000 in P_CT_RAT setting.
6.2.5.2
System Config.
▶
T/S Output Setting
Connection types and recovery delay time for 7 output connections can be set in
T/S Output.
Select 2. T/S Output category in System Config., then the following screen appears.
- 〉