 다기능 디지털 복합 보호계전기

 

K-PAM 5500 Series

20

21

Kyongbo Electric Co., Ltd.

Digital Integrated Protection Relay

 

K-PAM 10 Series

Category

Setting Range

Description

FUNCTION

DISABLED, ENABLED

Setting whether to use the function

ID NAME

8 ASCII Characters

Protection element name setting

PICKUP

47.00 ~ 65.00Hz (0.01Hz STEP)

Operation frequency setting

BLOCK VOLT

0.02 ~ 1.30pu (0.01pu STEP)

Minimum operating voltage setting

TIME DELAY

0.04 ~ 60.00s (0.01s STEP)

Operation delay time setting

RESET DLY

0.00 ~ 60.00s (0.01s STEP)

Reset delay time setting

  Contact Output Test Method

 ①  Press the MENU( 

MENU

 ) key on the initial screen

 ②  Use the UP ( 

 ) and DOWN ( 

 ) keys to move the ‘6.DEVICE CONFIG’ category, and then press the RIGHT 

     ( 

 

 

 ) Key.

 ③  Use the UP ( 

 ) and DOWN ( 

 ) keys to move the ‘11.TEST’ category, and then press the RIGHT ( 

 

 

 ) Key.

 ④  Use the UP ( 

 ) and DOWN ( 

 ) keys to move the ‘2.D/O TEST’ category, and then press the RIGHT ( 

 

 

 ) Key.

      After the password input screen pops up (Initial password 0000), enter the digital output TEST screen when 

ENTER KEY is input.

LCD SCREEN

D   /   O               T   E   S   T                       1   /   2

⇒     1   .   D   /   O         #   1     :     O   f   f
 

2   .   D   /   O         #   2     :     O   f   f

 

3   .   D   /   O         #   3     :     O   f   f

D   /   O               T   E   S   T                       2   /   2

 

4   .   D   /   O         #   4     :     O   f   f

 

5   .   D   /   O         #   5     :     O   f   f

TEST Method

(1)  In the D/O TEST screen, press the UP( 

 ), DOWN( 

 ) keys and press the ENTER( 

ENTER

 ) key at the 

position of the contact to be tested, the contact will change from Off to On and the contact will be output.

      When the ESC( 

ESC

 ) key is pressed, the output contact is reset.

(2)  If you press the UP( 

 ) or DOWN( 

 ) KEY, you can select another digital output. 

       In this state, if you press the LEFT ( 

 

 

 ) KEY, all the contacts will return to original state and come out 

of the screen.

▶ UFR Setting Method

 ①  After selecting ‘UFR (81U)’ in Protection Relay Element Setting Method ③, press the RIGHT ( 

 

 

 ) Key to enter 

the setting screen.

 ②  Use the UP ( 

 ), DOWN ( 

 ) KEY to move the category you want to set, and then enter the ENTER (

KEY to pop up the password input screen. (initial password 0000)

 ③  Use the UP ( 

 ), DOWN ( 

 ) KEY to change the setting value and then input ENTER ( 

ENTER

 ) KEY.

 ④  After completing the setting, input the LEFT ( 

 

 

 ) KEY to check whether the setting has been changed.

      When ENTER ( 

ENTER

 ) KEY is input, the setting is saved, and when ESC ( 

ESC

 ) KEY is input, the setting is canceled.

  How to check when the operation of the protection element (In case of fault)

①Check the Front

Fault is being held

The protection element is in operation, but the fault has reset.

② Check the protection relay element status window

 - Press the MENU( 

MENU

 ) key on the initial screen

 - Use the UP ( 

 ) and DOWN ( 

 ) keys to move the ‘4.STATUS’ category, and then press the RIGHT ( 

 

 

 ) Key.

 -  Use the UP ( 

 ) and DOWN ( 

 ) keys to move the ‘1.PROT STATUS category, and when RIGHT ( 

 

 

 ) Key is 

input, the following screen is displayed.

Содержание K-PAM 10 Series

Страница 1: ...K PAM 10 Series Digital Integrated Protection Relay User Manual...

Страница 2: ...elay K PAM 10 Series K PAM10Seriesisamulti functionaldigitalIntegrated protection relay that provides high precision measurement and reliable protection relay function for power supply and distributio...

Страница 3: ...E INPUT 7 EVENT LIST POWER D I STATUS CT RATIO OCR3 OVR2 REMOTE INPUT 1 DPR2 REMOTE INPUT 9 LED 1 DIGITAL OUTPUT 2 LEDS EVENT CLEAR FREQUENCY R I STATUS NCT RATIO OCGR2 UVR1 REMOTE INPUT 3 UPR2 REMOTE...

Страница 4: ...O MENU OCR1 DOCGR2 OCR3 OVGR2 OCGR2 UBOCR OCR2 VOLTAGE CURRENT OVGR1 OCGR1 SGR DOCGR1 EVENT LIST EVENT CLEAR FAULT LIST FAULT CLEAR PROT STATUS D I STATUS R I STATUS CB STATUS D O STATUS CB DO COUNT C...

Страница 5: ...a setting Right Key Used to move from the menu to the upper menu or to the right when setting Left Key Used to move from menu to sub menu or to move to the left when setting MENU Key Used to enter the...

Страница 6: ...ntact Capacity AC 250V 5A DC 125V 10A 6 4a_NO 7 3_4_COM 8 5b_NC For System Error Contact Capacity AC 250V 5A DC 125V 1 9 5_COM 10 DI 1 User defined Input Contact 11 DI 2 12 DI 3 13 DI COM 14 RS 485 Se...

Страница 7: ...t for details C I R C U I T B R E A K E R C O N T R O L E N T E R Y E S E S C N O C O N T R O L F A I L E D C B S T A T E D I S A B L E D If the front LOCAL REMOTE LED is lit as REMOTE pressing the L...

Страница 8: ...P OP OP RST ALL EVENT record setting Category Setting Range Description FUNCTION DISABLED ENABLED Setting whether to use the function ID NAME 8 ASCII Characters Protection element name setting ALGORIT...

Страница 9: ...REVERSE Operation direction setting MODE INST DT INV Operation mode setting TIME DELAY 0 04 60 00s 0 01s STEP Operation delay time setting CURVE IEC_NI IEEE_MI Inverse curve setting 12ea LEVER 0 01 1...

Страница 10: ...00 60 00s 0 01s STEP Reset delay time setting UVR Setting Method After selecting UVR 27 in Protection Relay Element Setting Method press the RIGHT Key to enter the setting screen Use the UP DOWN KEY...

Страница 11: ...position of the contact to be tested the contact will change from Off to On and the contact will be output When the ESC ESC key is pressed the output contact is reset 2 If you press the UP or DOWN KEY...

Страница 12: ...T A T U S P K P O P 1 O C R 1 A B C 2 O C G R 1 3 D O C G R P R O T S T A T U S P K P O P 1 O C R 1 A B C A B C 2 O C G R 1 3 D O C G R P R O T S T A T U S P K P O P 1 O C R 1 A B C 2 O C G R 1 3 D O...

Страница 13: ...voltage and frequency are 1 0 6 0 016 Hz and the frequency changed by 0 02Hz or more per at least 1 cycle is about 20 cycles about 0 3 sec for voltage A At this time the voltage should be at least 80...

Страница 14: ...Terminal T1 D O4_NO D O3 4_COM D O2_NO D O2_COM Aux Power 1 2 Terminal T2 FG 3 CHASSIS V10 A L1 B L2 C L3 D O1_NO 1 2 3 4 5 6 7 8 9 14 15 16 COM RS 485 8 7 VN IA IB IC IN C L R EVT Terminal T1 D O1_C...

Страница 15: ...rminal T2 FG 3 CHASSIS M11 9 10 11 12 13 14 15 16 CT A L1 B L2 C L3 D O1_NO 1 2 3 4 5 6 7 8 9 14 15 16 COM RS 485 1 2 VA 3 4 5 6 8 7 VB VC VN IA IB IC C L R EVT Terminal T1 D O1_COM D O3_NO D O5_NC D...

Страница 16: ...bolts on the corners of the enclosure mounted on the panel Remove the handle cover of the product loosen the screw raise the handle vertically as shown in and attach it to the enclosure After inserti...

Страница 17: ...K PAM 10 Series Digital Integrated Protection Relay User Manual...

Отзывы: