Introduction 

 

The PTS-30 time server is a standard time synchronization server. Support GPS, BDS, 
GLONASS,  IRIG-B  and  PTP time source, internal built-in TCXO, OXCO, Rubidium 
Oscillator  and multiple sources time sync automatic selection algorithm and 
Master/Slave clock redundant switch control    logical, which will perform GPS, BDS, 
GLONASS,  IRIG-B,  PTP  and  local clock System multiple  time source auto selection, 
sky/grounding  and master/slave clock backup. PTS-30  time server provides flexible 
time synchronization signal output slots which can help to configure different timing 
output interface channel. The output timing channels include PPS, PPM, PPH, IRIG-B 
(DC), IRIG-B (AC), Serial Time Signal (TOD etc.) etc. Both fiber and copper interfaces 
are supported. Plus, PTS-30 supports network sync time protocols NTP/SNTP/EEE1588 
v2.0. IEEE1588 works in several modes by the software configuration including 
grandmaster clock, slave clock and boundary clock. PTS-30 time server also has alarm 
contact output. PTS-30 time server provides 5.7 inch color touch screen as HMI and 
the visualization interface is available for work status monitoring and parameters 
setting. Meanwhile, PTS-30 time server is designed to send timing source status and 
clock status to control center by IEC61850, IEC60870-5-104, IEC60870-5-101, DNP3.0, 
and Modbus etc. PTS-30 time server also supports WEB and SNMP to manage system.

- 2 - 

Содержание PTS-30

Страница 1: ...PTS 30 Time Server WEB Manual Kyland Technology Shanghai Co Ltd Version Copyright R7...

Страница 2: ...Kyland Technology Shanghai Co Ltd Room 802 Building 5 No 3000 Longdong Avenue Pudong District Shanghai China Tel 86 21 80321288 Fax 86 21 80321289...

Страница 3: ...2 Clock Status 6 3 2 Configuration 6 3 2 1 Sync Source Settings 7 3 2 2 Clock Settings 8 3 2 3 NTP Settings 10 3 2 4 PTP Settings Optional 10 3 2 5 Output Settings 12 3 2 6 Network Settings 14 3 2 7...

Страница 4: ...e different timing output interface channel The output timing channels include PPS PPM PPH IRIG B DC IRIG B AC Serial Time Signal TOD etc etc Both fiber and copper interfaces are supported Plus PTS 30...

Страница 5: ...gin WEB management system Before you access WEB management system of PTS time server please confirm you might access this Ethernet port if find any problems you should check the network whether or not...

Страница 6: ...t system you might directly click this and then system will go to original login screen and wait user to input login information again 2 3 Languages The default language is English the WEB management...

Страница 7: ...possible Press Status to go to the status screen on the top of navigation bar The status screen will be shown as Figure 3 Status Screen 3 1 1 Source Status Press Source Status on the left navigation b...

Страница 8: ...status screen The clock status screen will be shown as Figure 5 Clock Status Screen To show the current selected source inside temperature power grid measurement frequency and the current work status...

Страница 9: ...ll be shown as Figure 7 Sync Source Setting Screen Press Save button to save the current setting when you change setting Items Parameters Description Channel Type UBLOX5 UBLOX8 AT3340 HWA210B HWA210L...

Страница 10: ...ync source PEER is redundancy sync source and NONE is anything to do Input Channel FI1 FI2 To set IRIG B1 B2 input time signal Time Format DC DC To set IRIG B1 B2 input format including DC positive po...

Страница 11: ...time zone display TAI UTC Offset 35s Set time zone offset between TAI and UTC Output Mode Always Lock Always means time server has output signals in any status Lock means time server only has output...

Страница 12: ...Time 00 00 24 00 3 2 3 NTP Settings Press NTP on the left navigation bar to show NTP setting screen The NTP setting screen will be shown as Figure 9 NTP Setting Screen Press Save button to save the cu...

Страница 13: ...e rate of PTP master clock Setting value is n actual interval is 2n seconds Valid range is from 8 to 4 and Stop Default value is Stop Delay Measurement Interval 8 4 Stop Set delay measurement rate Set...

Страница 14: ...information Master Coordination YES NO Set master coordination function with BMC 3 2 5 Output Settings Press OUTPUT on the left navigation bar to show output setting screen The default output setting...

Страница 15: ...Set the coding format for serial message Interface BaudRate 300 115200 Set the working baud rate for serial port ranging from 300 to 115200 Second Compensation 0s Set second compensation offset PPS Co...

Страница 16: ...Set IRIG B output signal polarity If select AC the output setting screen will be shown as Figure 14 Output Setting Screen AC Items Parameters Description Peak to Peak 3 OV 12 0V Set the peak to peak...

Страница 17: ...Mask Address ETH0 255 255 255 0 ETH1 255 255 255 0 ETH2 255 255 255 0 ETH3 255 255 255 0 Set ETH0 1 2 3 Subnet mask address Interface Mode Auto Force PTS 30 can provide more network type One of them c...

Страница 18: ...rver Figure 16 TMS Setting Screen Press Save button to save the current setting when you change setting Press GOOSE channel to select GOOSE publisher and subscriber channel The GOOSE publisher GOOSE P...

Страница 19: ...t GOOSE message Trigger Period 0 255 Set period to send out GOOSE message the 0 means no data change and the non zero means system will send a new GOOSE when the current time at PPS PPM or PPH can be...

Страница 20: ...e bit position of byte item 3 3 System The WEB management system supports to manage Gateway Route information and to backup and restore configuration file in the same time it also supports firmware ma...

Страница 21: ...route information 3 3 2 Route Press Route on the left navigation bar to manage Route information The route screen will be shown as Figure 21 Route Screen The current routing table will be listed on th...

Страница 22: ...configuration file 3 3 4 Firmware Press Firmware on the left navigation bar to upgrade firmware The firmware screen will be shown as Figure 23 Firmware Screen Press Download to update the new firmware...

Страница 23: ...only has read only permissions V3 does not have default value Notes Any modifications about SNMP should reboot PTS 10 to activate it 3 4 Management The WEB management system supports to change user p...

Страница 24: ...e 26 Change Password Screen Please Save to confirm the new password 3 4 2 Reboot Press Reboot on the left navigation bar to reboot device The reboot screen will be shown as Figure 27 Reboot Screen Pre...

Страница 25: ...Figure 11 Output Setting Screen 12 Figure 12 Output Setting Screen SO 13 Figure 13 Output Setting Screen O1 O2 O3 O4 O5 13 Figure 14 Output Setting Screen AC 14 Figure 15 Network Setting Screen 15 Fig...

Отзывы: