Kyland Technology (Shanghai) Co., Ltd PTS-DR200 Time Server
- 35 -
Items
Parameters
Description
Local: Make output time working at Local format.
IRIG-B
Mode
Even
Odd
Set IRIG-B check code for O4.
Even: Use Even mode check code to code IRIG-B signal;
Odd: Use Odd mode check code to code IRIG-B signal.
IRIG-B
Polarity
+
-
Set IRIG-B output signal polarity for O4.
+: positive polarity DC, high level is 1;
-: negative polarity DC, low level is 1.
Press ‘Save’ button to save the current setting when you change setting.
If select ‘O5’ in Channel Group, the setting screen will be shown as:
[Figure 3-22] Output Setting Screen (O5)
Table 21 – Output Setting (O5)
Items
Parameters
Description
IRIG-B
Second
Compensation
0s
Set second compensation offset for O5.
Unit is second(s);
Range is between -999999999s and 999999999s.
Default value is 0s.
IRIG-B
PPS
Compensation
0ns
Set PPS compensation offset for O5.
Unit is nanosecond(ns);
Range is between -250000000ns and 250000000ns.
Default value is 0ns.
IRIG-B
Time
Format
UTC
TAI
Local
Set reference time for IRIG-B output signal of O5.
UTC: Make output time working at UTC format;
TAI: Make output time working at TAI format.
Local: Make output time working at Local format.