D.

E.

Condensate Tank & High Level Alarm - 

All KPAC II models come standard with 

an internal condensate tank. The tank is equipped with an overflow safety cut-off. When 
the tank is full, the safety will automatically shut down your unit, sound an audible alarm 
and display a fault code (

CF

) this prevents accidental flooding of the conditioned space. 

To continue operation when bottle is filled, see section II:B.

Service Ports - 

Located in the filter access compartment in the front of your KwiKool 

below the control panel. This gives service personal a connection point for service 
gauges to monitor the operating pressures of your KPAC II refrigeration system.

VI / Application Requirements

Air Temperature Requirements -

 

The environmental requirements of your 

KwiKool unit at the installation site are 60 to 110 degrees F for the condenser make-up 
air located on the back of the unit. 

If the unit is operated in an environment above 110 

the high pressure switch may trip, stopping the unit’s compressor. You also may 

notice diminished performance. The High Pressure Switch type is a manual reset. The 
reset switch is located in the condenser make-up air inlet on the back of the system. 
Reset the unit by pressing the button labeled HP Reset. 

Standard air-cooled KwiKool 

models are not designed to operate at temperatures below 60 degrees F. Low-

ambient temperature controls must be special ordered at an additional cost.

 

Temperatures below 60 degrees F will cause freezing and or diminished performance 
and can void your warranty.

Capacity & Temperature Settings - 

Sizing of our units is based on matching 

capacity to a specific heat load while maintaining a 72 degree F temperature.  In order 
to reach temperatures below 72 degrees F, the unit must have extra capacity.  

Positioning of Unit -

 

Do not place your KwiKool unit in direct sunlight, the unit 

should be positioned so that the output of the unit can be focused as close to the heat 
generating equipment as possible with the front grill fully exposed.  Do not block the 
front of the unit, since this will cause a restriction in the airflow and can cause low 
performance and/or evaporator coil freezing. The KPAC II will take condenser make-up 
air from the area of placement and cannot be ducted, the inlet for the condenser 
make-up air is located in the rear of the unit and will not allow for the back of the unit to 
be placed flat against a wall or fixed object, not allowing at least 5 or 6 inches of space 
between the inlet and a wall or fixed object will cause decreased performance and or 
high pressure safety trip. 

B.

A.

VII / Maintenance

Air Filters -

 

Your KwiKool unit comes from the factory with filters installed on the 

evaporator inlet to prevent dust and debris from entering the system and circulating in 
the conditioned space, factory installed filters are a disposable type and must be 
periodically checked and replaced based on the air quality of your conditioned space. 

Failure to maintain the filters will cause restricted air flow and low overall unit 

performance.

 The air filter is located on the front of your KwiKool unit below the 

control, release the 2 slotted fasteners on the access door to open.

A.

C.

Содержание KPAC II series

Страница 1: ...KPAC II Operation Manual S E I R E S...

Страница 2: ......

Страница 3: ...ined for future reference Section I Unit Components Page 3 Section II Assembly and Installation Page 4 5 Section III Operational Safeguards Page 6 Section IV System Operation Page 6 8 Section V Built...

Страница 4: ......

Страница 5: ...nents KPAC 1411 1 800 KWIKOOL ETL LISTED CONFORMS TO ANSI UL CERTIFIED TO CAN CSA 22 2 NO 2 LEGEND 1 Cold Air Return 4 Condenser Air Inlet 2 Control Pad 5 Condenser Air Outlet 3 Cold Air Supply 6 Powe...

Страница 6: ...tinue operation of your KPAC II the collection bottle must be removed emptied and then re installed Turning the KPAC II to off will stop the audio alarm Remove the float switch jack by pulling it stra...

Страница 7: ...ad without pressurizing and coming back into your condi tioned space Discharge make up air will come from your conditioned space and create a negative pressure in the conditioned area Determine if you...

Страница 8: ...mage the compressor Do not place objects on top of your unit Do not insert your hand or any other object into the cold air supply chutes Do not operate your KwiKool system with its service doors open...

Страница 9: ...operates when the compressor is running When the fan is set to on the fan runs continuously as long as the unit is in the ON position The fan speed window will be blank on these models Up and Down Arr...

Страница 10: ...mperature falls below 99 degrees F FAN If the unit was previously set to the fan mode then FAN will be displayed and the fan will start to run System Operation 1 Page 8 b The lowest set point temperat...

Страница 11: ...hed performance and can void your warranty Capacity Temperature Settings Sizing of our units is based on matching capacity to a specific heat load while maintaining a 72 degree F temperature In order...

Страница 12: ...ntain those special environments Call your nearest KwiKool Distributor or 1 800 594 5665 for help or for questions about other applications IX Fault Codes Your KwiKool Iceberg System incorporates a se...

Страница 13: ...or not in the correct operational MODE Wait 2 minutes review System Operations guide Fault Possible Cause Possible Solution Power is supplied but control is blank Low voltage circuit is not engaged C...

Страница 14: ...return air temperature out of factory specifications Evaporator door open mechanical system malfunction Direct supply return air to area of highest heat load check for blocked air flow from the supply...

Страница 15: ......

Страница 16: ...Revision 062016...

Отзывы: