NOTE
When Start Command is available, it is possible to avoid the switching off and on
of the generator, resetting the following protections by commutating OFF and ON
the start command switch:
- Overload, - Over temperature,
- Output under voltage (not severe), - Output under voltage (severe).
In case of more than a fault condition at the same time, the priority of
signalization will be as per the following:
1.
BUS Overvoltage
2.
Overload condition
3.
Over temperature.
11.10. M
ESSAGING
S
IGNALS
DESCRIPTION
TYPE
(SEEN FROM
INVERTER)
STATUS
CONDITION
0
Inverter temperature stays below 55±5°C
11.10.1 Inverter Temperature
5
OUTPUT
1
Inverter temperature overcomes 55±5°C
0
Inverter working in nominal range (no limiting)
11.10.2 Inverter Status
5
OUTPUT
1
Inverter switched OFF or limiting
0
Inverter output voltage higher than 48V
RMS
11.10.3 Dangerous Voltage
5
OUTPUT
1
Inverter output voltage lower than 48V
RMS
CLOSE
Inverter starts to generate
11.10.4 Start Command
6
INPUT
OPEN
Inverter stops to generate
5
See Figure 14 for signal interface.
6
See Figure 15 for signal interface.