GCU-20 

Automatic Engine Control Unit 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

WARNING 

Disconnect  all  electric  power  to  the  machine  before 
installation. 

 

Protection Functions 

Engine fail to start   

Engine tries 3 times to start 

Engine Low Oil Pressure Protection 

Shutdown activated after 3 seconds 
Oil Pressure Switch Type NO or NC 

Auxiliary Shutdown 

Shutdown activated after 3 seconds delay by NO contact 

Engine High Water temperature Protection 

Shutdown activated after 3 seconds delay by NO contact 

Engine Over-speed Protection 

Shutdown activated after 3 seconds 
50 Hz activated at 55 Hz 

– 60 Hz activated at 66 Hz 

Engine Under-Speed Protection 

Shutdown activated after 5 seconds 
50 Hz activated at 45 Hz 

– 60 Hz activated at 54 Hz 

No Speed Signal Present Protection 

Shutdown activated after 5 seconds (MPU use only) 

 

Icon Reference Table 

ICON 

DESCRIPTION 

ACTION 

 

Low Oil Pressure Alarm 
Auxiliary Alarm (Flashing) 

Shutdown 

 

High Water Temperature Alarm 

Shutdown 

 

Over Crank Alarm 

Shutdown 

 

Wrong speed Alarm 
No Speed Signal Alarm (Flashing) 

Shutdown 

 

Engine Running Indicator 
Engine IDLE Indicator (Flashing) 

 

 

Engine Pre-Heat Indicator

 

Pre-Heat 

 
 

 

 
 
 
 
 
 

 

Physical Dimensions 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Mounting Pattern 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Installing Panel 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

 

 

Содержание GCU-20

Страница 1: ... speed Protection Shutdown activated after 3 seconds 50 Hz activated at 55 Hz 60 Hz activated at 66 Hz Engine Under Speed Protection Shutdown activated after 5 seconds 50 Hz activated at 45 Hz 60 Hz activated at 54 Hz No Speed Signal Present Protection Shutdown activated after 5 seconds MPU use only Icon Reference Table ICON DESCRIPTION ACTION Low Oil Pressure Alarm Auxiliary Alarm Flashing Shutdo...

Страница 2: ... lamps Battery 10A Model GCU 20 No Speed Signal Flash Engine Running Engine IDLE Flash Pre Heat Wrong Speed J1 J2 J4 J3 Lamp Test Low Oil Pressure High Temp Over Cranking Auxiliary Alarm Flash Remote Annunciator J7 J6 J5 Using with MPU If you use the MPU for speed sensing instead of the generator frequency you must set Switch 6 to ON and depending on flywheel size different generators has a differ...

Страница 3: ...ntinuous flashing in idle indicating the status is IDLE If engine idle is not used set adjustment E full counterclockwise Sixth if the engine does not start the first time the module will try again to start the engine 2 more times and stop after the third try If the generator fail to start move the select switch to the OFF Reset position Find out why the engine failed to start before making any mo...

Страница 4: ... Oil Lamp J3 RW J1 J2 Remote Annunciator RA 20 J4 J5 J6 J7 Battery 10A RA RI Batt Lamp Test SW Low Oil SW High Temp SW Auxiliary SW Acc ON Relay Idle Relay Model GCU 20 Wrong Speed Lamp High Temp Lamp Over Crank Lamp Engine Run Lamp Common Alarm Lamp Warm up Relay 1 Auxiliary SW High Temp SW Lamp Test SW Low Oil SW 2 4 3 Acc ON Relay Batt 23 21 22 Start Relay Stop Relay Low Oil Lamp Model GCU 20 B...

Отзывы: