EA341

 

2.4 

A  frequency  measuring  circuit  continually 
monitors  the  shaft  speed  of  the  generator  and 
provides under-speed protection of the excitation 
system by reducing the generator output voltage 
proportionally  with  speed  below  a  pre-settable 
threshold.  A  further  enhancement  of  this  feature 
is an adjustable VOLT per Hertz slope to improve 
engine recovery  time on turbo charged engines. 
Soft start circuitry is included to provide a smooth 
controlled build up of generator output voltage. 

 
2.5 

Uncontrolled excitation is limited to a safe period 
by  internal  shutdown  of  the  AVR  output  device. 
This condition remains latched until the generator 
has stopped. 

 
2.6 

Provision is made for the connection of a remote 
voltage trimmer, allowing the user fine control of 
the gene

rator’s output. 

 
2.7 

An 

analogue 

input 

is 

provided 

allowing 

connection  to  a  controller  or  other  external 
devices with compatible output. 

 
2.8 

The AVR has the facility for droop CT connection, 
to  allow  parallel  running  with  other  similarly 
equipped generators. 

NOTE :

 

(1)  Derate linearly from 3.7A at 50 

˚C to 2.7A at 70 ˚C. 

 
(2)  The  stated  voltage  regulation  may  not  be 

maintained  in  the  presence  of  certain  transmitted 
radio  signals.  Any  change  in  regulation  will  fall 
within  the  limits  in  Criteria  B  of  S.EN.61000-6-2  : 
2001. 

 
(3)  After 10 minutes. 
 
(4)  Applies  to  Mod  status  E  onwards.  Generator 

de-rate may apply. Check with factory. Factory set, 
semi-sealed, jumper selectable. 

 
(5)  Any  device  connected  to  the  analogue  input  must 

be fully  looting (galvanically  isolated from ground), 
with an insulation strength of 500 Vac. 

 
(6)  Non condensing. 
 
 
 
 

 

SECTION 3 : SUMMARY OF AVR CONTROLS 

CONTROL

 

FUNCTION

 

DIRECTION

 

VOLT 

To adjust generator output voltage 

Clockwise increases output voltage 

STABILITY 

To prevent voltage hunting 

Clockwise increase the damping effect 

UFRO 

To set the UFRO knee point 

Clockwise reduces the knee point frequency 

DROOP 

To set the generator droop to 5% at 0 pf 

Clockwise increases the droop 

TRIM 

To optimize analogue input sensitivity 

Clockwise increases the gain or sensitivity 

EXC 

To set the over excitation cut off level 

Clockwise increase the cut off level 

DIP 

To set the frequency related voltage dip 

Clockwise increases the voltage dip 

Содержание EA341

Страница 1: ...Qianfu St Qianzhen Dist Kaohsiung City 80664 Taiwan EA341 Generator Automatic Voltage Regulator Operation Manual Self Excited Automatic Voltage Regulator Compatible with Newage MX341 All manufacturer names and numbers are used for reference purpose only and do not imply that any part is the product of these manufacturer ...

Страница 2: ...al Voltage Thermal Drift Less than 3 at temperature range 40 to 70 C Soft Start Ramp Time 2 seconds 10 Environment Operating Temperature 40 to 70 C Static Power Dissipation Storage Temperature 40 to 85 C Max 12 watts Relative Humidity Max 95 Vibration 3 3 Gs 100 2K Hz Analogue Voltage Input Input Resistance 1K ohm Dimensions Max Input 5 Vdc 150 0 L x 135 0 W x 48 0 H mm Sensitivity 1V for 5 genera...

Страница 3: ...ection to allow parallel running with other similarly equipped generators NOTE 1 Derate linearly from 3 7A at 50 C to 2 7A at 70 C 2 The stated voltage regulation may not be maintained in the presence of certain transmitted radio signals Any change in regulation will fall within the limits in Criteria B of S EN 61000 6 2 2001 3 After 10 minutes 4 Applies to Mod status E onwards Generator de rate m...

Страница 4: ...e stability control anti clockwise until the generator voltage starts to become unstable The optimum or critically damped position is slightly clockwise from this point i e where the machine VOLT are stable but close to the unstable region 4 3 Under Frequency Roll Off UFRO Adjustment 4 3 1 The AVR incorporates an under speed protection circuit which gives a VOLT Hz characteristic when the generato...

Страница 5: ...RNING Please make sure you have read and understand the contents of the instruction manual prior to installation Incorrect wiring connection may result in irreversible damage to the product and other equipments SECTION 5 FITTING AND OPERATING Refer to generator wiring diagram for connection details ATTENTION 1 AVR can be mounted directly on the engine genset switchgear control panel or any positio...

Страница 6: ... A2 S1 S2 J1 J2 J3 J4 J5 J6 J7 J8 K2 K1 P2 P3 P4 XX X 3 2 2 1 FREQUENCY SENSING SELECTION INDICATOR C B A 3 2 1 STABILITY DIP LED SELECTION k1 k2 linked for normal operation 3 1 4P 60HZ 3 2 4P 50HZ 2 1 6P 50HZ NO LINK 6P 50HZ C A 90KW EA341 G Generator P4 P3 P2 PMG X XX 3 Bridge T 220V S R S1 C T S2 1 2 For external adjusted 1K 2 3 Exciter Figure 2 Disposition Drawing Figure 3 Wiring Drawing Note ...

Отзывы: