background image

 

___________________________________________________________________________________________ 

EA321

 

4.6 

Excitation (EXC) Adjustment 

This  adjustment  is  set  and  sealed  in  the  works  and 
should  not  be  tampered  with.  An  over  excitation 
condition is indicated by the illumination of the red LED 
which  also  indicates  under-speed  running  and 
over-volt. 
 
The  generator  must  be  stopped  to  reset  an 
over-excitation trip. 
 

4.7 

DIP Adjustment 

4.7.1  This feature is mostly used when the generator is 

coupled  to  turbo  charged  engines  with  limited 
block  load  acceptance.  The  feature  works  by 
increasing the V/Hz slope to give greater voltage 
roll off in proportion to speed. 

 
4.7.2  With  the  DIP  control  fully  anti-clockwise,  the 

generator voltage will follow the normal V/Hz line 
as  the  speed  falls  below  nominal.  Turning  the 
DIP  control  clockwise  provides  greater  voltage 
roll off aiding engine recovery. 

 

4.8 

RMS Voltage Adjustment 

When  the  generator  is  operating  with  a  relatively  low 
power  factor  load,  or  other  reasons  change  the  output 
power  waveform  when  adding  load,  this  will  then  cause 
the AVR sensing the deviated voltage. 
 
The  RMS  control  on  the  AVR  can  reduce  the  voltage 
variations caused by the output waveform changes. This 
improves voltage regulation. 

 
4.9 

DWELL 

This  feature  is  mostly  used  when  the  generator  is 
coupled  to  turbo  charged  engines  with  limited  block 
load  acceptance.  The  feature  works  by  introducing  a 
delay  between  speed  recovery  and  voltage  recovery 
and allows a greater DIP setting without instability. 

With  the  DWELL  control  fully  anti-clockwise,  the 
generator voltage will follow the V/Hz line. Turning the 
DWELL  control  clockwise  increase  the  delay  time 
between speed recovery and voltage recovery. 

 
4.10  Current Limit (I LIMIT) Adjustment 

This feature is mostly used to limit short circuit current or 
to  provide  a  current  limit  on  motor  starting.  To  use  this 
feature, current limit CT’s of the correct ratio need to be 
connected  to  the  AVR  S1,  S2  terminals.  There  is  an 
internal  time  limit  of  10  seconds.  Consult  the  factory 
before using this feature. 
 

4.11  Over Voltage (OVER V) Adjustment 

This adjustment is set and sealed in the works and should 
not  be  tampered  with.  An  over  voltage  condition  is 
indicated  by  the  illumination  of  the  red  LED  which  also 
indicates  under-speed  running  and  over-excitation.  The 
generator must be stopped to reset an over-voltage trip. 

 
4.12  RAMP 

The AVR includes a soft start or voltage ramp-up circuit 
to  control  the  rate  of  voltage  build  up,  when  the 
generator  runs  up  to  speed.  This  is  normally  pre-set 
and  sealed  to  give  a  voltage  ramp-up  time  of 
approximately  3  seconds.  If  required,  this  can  be 
adjusted between the limits defined in the specification. 
 

WARNING 

Please  make  sure  you  have  read  and  understand 
the  contents  of  the  instruction  manual  prior  to 
installation.  Incorrect  wiring  connection  may 
result  in  irreversible  damage  to  the  product  and 
other equipments.

 

 
 

 

SECTION 5 : FITTING AND OPERATING (Refer to generator wiring diagram for connection 
details)

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

ATTENTION 

1.  Leave  sufficient  space  for  the  high  output  resistor  to 

dissipate heat. Install the AVR with an up right position 
where the high output resistor is above heat sink. 

2.  AVR  can  be  mounted  directly  on  the  engine, 

genset,  switchgear,  control  panel,  or  any  position 
that  will  not  affects  operation.  For  dimension 
reference, please see Figure 1. 

3.  All  voltage  readings  are  to  be  taken  with  an 

average-reading voltmeter Meggers and high-potential 
test  equipment  must  not  be  used.  Use  of  such 
equipment could damage the AVR. 

4.  Improper  setting of  under-frequency  protection  could 

cause the output voltage of the unit to drop or become 
unstable  under  with  changes  in  load.  Avoid  making 
any changes to the U/F setting unless necessary. 

5. Set  the  O/E  potemtiometer  at  max.  position  when 

paralleling. 

DWELL

UFRO

DIP

RMS

STABILITY

VOLTS

DROOP

TRIM

I/LIMIT

EXC. TRIP

OVER / V

INDICATOR

LED

RAMP

Resistor

Resistor

114.5

65.0

203.5

129.6

153.6

20.0

43.5

  5.5

 

Figure 1

 

Outline Drawing 

Содержание EA321

Страница 1: ...201 Qianfu St Qianzhen Dist Kaohsiung City 80664 Taiwan EA321 Generator Automatic Voltage Regulator Operation Manual Use with PMG brushless generators Compatible with Newage MX321 All manufacturer names and numbers are used for reference purpose only and do not imply that any part is the product of these manufacturer ...

Страница 2: ...ty range 0 5 1A Intermittent 7A for 60 secs Resistance Min 15 ohm Under Frequency Protection Factory Presets Set point 95 Hz External Voltage Adjustment Slope 100 300 down to 30 Hz Max 10 5K ohm 1 watt potentiometer Over Excitation Protection Voltage Regulation Set point 120 Vdc Less than 0 5 RMS with 4 engine governing Time delay 8 15 secs Build Up Voltage Voltage Thermal Drift 5 Vac residual vol...

Страница 3: ...mote voltage trimmer allowing the user fine control of the generator s output 2 7 An analogue input is provided allowing connection to a controller or other external devices with compatible output 2 8 The AVR has the facility for droop CT connection to allow parallel running with other similarly equipped generators NOTE 1 Derate linearly from 3 7A at 50 C to 2 7A at 70 C 2 The stated voltage regul...

Страница 4: ... stability control anti clockwise until the generator voltage starts to become unstable The optimum or critically damped position is slightly clockwise from this point i e where the machine volt are stable but close to the unstable region 4 3 Under Frequency Roll Off UFRO Adjustment 4 3 1 The AVR incorporates an under speed protection circuit which gives a VOLT Hz characteristic when the generator...

Страница 5: ...ent limit CT s of the correct ratio need to be connected to the AVR S1 S2 terminals There is an internal time limit of 10 seconds Consult the factory before using this feature 4 11 Over Voltage OVER V Adjustment This adjustment is set and sealed in the works and should not be tampered with An over voltage condition is indicated by the illumination of the red LED which also indicates under speed ru...

Страница 6: ...1 Droop Stability U V W Trim Dwell Dip LED UFRO Rms Selection Frequency Volts 4P60HZ 1 2 3 No link 6P50HZ 4P50HZ 6P60HZ I Limit EA321 Stability 550KW 90 550KW 90KW Indicator EA321 G Generator P4 P3 P2 PMG X XX 3 Bridge S1 T S2 220V C T S R C T S1 S2 S1 C T S2 1 2 For external adjusted 5K 6 7 8 K1 K2 B0 B1 E0 E1 U V W 1 2 3 A B C Exciter Figure 2 Disposition Drawing Figure 3 Wiring Drawing Note Whe...

Отзывы: