Full Wave
Half Wave
50Hz
60Hz
Figure. 8
5.2.3 Generator Frequency Selector
Select Generator frequency for U/F protection (Factory preset 60Hz)
50 Hz system factory presets knee point at 45 Hz
60 Hz system factory presets knee point at 55 Hz
5.2.4 Half Wave / Full Wave Selector
Select half wave or full wave output according to Generator excitation voltage in full load (Factory preset Half Wave).
If generator excitation voltage is greater than 60Vdc in Full load, must select Full Wave output.
If generator excitation voltage is less than 30Vdc, must select Half Wave output.
ATTENTION
※
Do not change the Under Frequency setting or Half Wave / Full Wave setting when generator is