ADVR-12

 

3.1 

DROOP Adjustment (DROOP) 

 
When  operating  in  parallel  the  AVR  increases  or 
decreases its voltage output when phase current leads 
or  lag  the  voltage.  The  range  of  this  increase  or 
decrease can be preset by the DROOP adjustment. 
 

3.2 

Voltage Adjustment (VOLT) 

 
Generator rated output voltage adjustment. Must be in 
agreement  with  the  DIP  Switch  SW5  voltage  range 
setting. 
 
180 

 260 Vac @ 220 Vac SW5 OFF 

330 

 520 Vac @ 440 Vac SW5 ON 

 

3.3 

Under Frequency Adjustment (U/F) 

 
When  generator  RPM  falls  below  the  knee  point,  the 
under frequency protection circuit will activate and the 
voltage  and  frequency  begin  to  decrease  in  linear 
descend. 
 
Select  frequency  50  Hz  or  60  Hz  according  to  the 
generator in use. 
 

3.4 

Stability Adjustment (STAB) 

 
Correct adjustment of STAB setting must be conducted 
while  the  generator  is  operating  without  load.  First 
adjust the STAB potentiometer (POT) clockwise to the 
point the voltage becomes unstable, then adjust it back 
slightly,  anti-clockwise  (About  1/5  turn).  This  is  point 
the  voltage  just  reaches  the  critical  point  (Knee  point) 
of  stabilization,  where  the  voltage  is  stable  yet  very 
close to becoming unstable. 
 

3.5 

TRIM Adjustment (TRIM) 

 
When terminals 2 & 3 are biased with a DC voltage (-5 

  +5V),  the  TRIM  is  used  to  adjust  the  influence  this 

DC has on the output voltage of the AVR. If the TRIM 
(POT) is adjusted fully counter-clockwise the AVR DC 
output  will  not  be  influenced  by  any  bias  voltage. 
Conversely,  if  the  TRIM  is  adjusted  fully  clockwise, 
then any signal will produce the maximum 10% effect. 
 

3.6 

U/F DIP Adjustment (DIP) 

 
When  U/F  protection  is  activated-,  the  voltage  droop 
ratio  can  be  adjusted  via  the  DIP  VR.  The  adjustable 
range is 3 

 10 V/Hz. 

 

3.7 

Over Excitation LED (O/E) 

 
Indicator  illuminates  when  the  generator  is  in 
Over-Excitation protection. 
 
Set point 125 Vdc +/- 5% @ 220 Vac. 
 

●  DIP  SW-3  switch  ON,  Over  Excitation  Protection 

Disabled.  If  over  excitation  occurs,  the  O/E  LED 
turns  on,  but  the  AVR  WILL  NOT  shutdown 
excitation. 

●  DIP  SW-3  switch  OFF.  Over  Excitation  Protection 

activated.  If  over  excitation  occurs,  the  O/E  LED 
turns on and the AVR will shutdown excitation. 

 

3.8 

Under Frequency Protection LED (U/F) 

 
Indicator  illuminates  when  the  generator  is  in  U/F 
Under-Frequency protection. 
 

SECTION 4 : CONNECTION TERMINAL 

TERMINAL 

DESCRIPTION 

CH GND 

Ground 

Analogue Voltage Input 

Connect  4  &  7  for  onboard  voltage 
adjustment. 
Connect  10K  ohm  VR  to  6a  &  7  for 
external  voltage  adjustment.  (keep  4  & 
7 Open) 

Current Transformer (CT) 1A input 

5a 

Current Transformer (CT) 5A input 

Current Transformer (CT) common 

6a 

Bridge selection common 

Connect  4  &  7  for  onboard  voltage 
adjustment. 
Connect  10K  ohm  VR  to  6a  &  7  for 
external  voltage  adjustment.  (keep  4  & 
7 open) 

No use (Null) 

Connect  9  &  6a  for  3  phase  sensing 
connect. 
Keep  9  &  6a  open  for  single  phase 
sensing. 

20 

Single or Three phase sensing input 

22 

Single or Three phase sensing input 

24 

Three phase sensing input 
Connect  22  &  24  for  Single  phase 
sensing input. 

26 

Three phase power input 

28 

Single or Three phase power input 

30 

Single or Three phase power input 

F1 

Positive excitation output (+) 

F2 

Negative excitation output (-) 

 

Содержание ADVR-12

Страница 1: ...Manual Self Excited Automatic Voltage Regulator For use in Brushless SHUNT PMG and Auxiliary Winding Compatible with Basler AVC63 12 AVC125 10 CATERPILLAR VR6 Kato K65 12B K125 10B Leroy Somer 202 8634 regulators Use with KUTAI IVT 1260 IVT 2460 add on module can boost generator motor starting capacity All manufacturer names and numbers are used for reference purpose only and do not imply that any...

Страница 2: ...20 Vac 3 Phase 50 Hz system presets knee point at 45 Hz Current Continuous 12A 60 Hz system presets knee point at 55 Hz Intermittent 20A for 10 secs Resistance 5 ohms power input 110 Vac Over Excitation Protection 11 ohms power input 220 Vac Set point 125 Vdc 5 power input 220 Vac Fuse Spec Slow blow 6 3 x 32mm 12 5A 500V Inverse time curve This function can be turned off External Voltage Adjustme...

Страница 3: ...est equipment must not be used Use of such equipment could damage the AVR 3 Secure all wiring connections Do not install AVR in a high vibration area to avoid loose connections For safety do not touch the heat sink while in operation 4 Improper setting of under frequency protection could cause the output voltage of the unit to drop or become unstable under with changes in load Avoid making any cha...

Страница 4: ...ed by any bias voltage Conversely if the TRIM is adjusted fully clockwise then any signal will produce the maximum 10 effect 3 6 U F DIP Adjustment DIP When U F protection is activated the voltage droop ratio can be adjusted via the DIP VR The adjustable range is 3 10 V Hz 3 7 Over Excitation LED O E Indicator illuminates when the generator is in Over Excitation protection Set point 125 Vdc 5 220 ...

Страница 5: ...Three Phase Sensing SHUNT Figure 4 Single Phase Sensing PMG or Auxiliary Winding S T R 20 GEN 22 24 26 28 30 F1 F2 CH GND 2 3 4 5 5a 6 6a 7 8 9 CT ADVR 12 FIELD F F Sensing Power PT1 PT2 S T R 20 22 24 26 28 30 F1 F2 CH GND 2 3 4 5 5a 6 6a 7 8 9 CT ADVR 12 Sensing Power PMG GEN CT FIELD F F PT1 Figure 5 Three Phase Sensing with power transformer If sensing or power voltage differs from ADVR 12 add...

Страница 6: ...ohms 1 watt Adjustable range is the same VOLT range 4 Sensing Voltage can be set from 220 440 Vac Program SW5 correctly 5 For single phase sensing bridge 20 22 and open 6a 9 6 When using PT1 of capacity 100VA must pay attention that the voltage and capacity of transformer PT2 has adequate excitation output Use only replacement fuses specified in this user manual Appearance and specifications of pr...

Отзывы: