8. Start-up  

The following points have to be noted when starting up:  
 

8.1. Checks before switching on the auxiliary energy  

Before starting up the device, check whether  

the wiring has been produced correctly as shown in the wiring diagram,  

the auxiliary energy corresponds to the details on the type plate,  

the ambient conditions match the details in the technical data. 

 

8.2. Checks after switching on the auxiliary energy  

After switching on the auxiliary energy, check whether  

the desired functions are set at jumpers and speed controllers.

 

 

9. Technical data 

 

Rated voltage:                  

100-240V AC or 24V ±10% AC/DC 

Rated consumption: 

< 3 VA 

Contact: 

2 two-way contacts, potential-free 

Switching voltage: 

max.  250 V AC 

Switching current: 

max. 8 A 

Electric connection: 

2.5 mm² (sensor 1.0 mm²), screw terminals, 3 x M16 (1 x M12) 

Protection class: 

II 

Type of protection: 

IP65 housing / IP54 sensor, EN 60529  

Flow speed: 

0.2 … 10 m/s (wearer appealing in the range of 0.2 – 1.0 m/s) 

Start delay: 

15 ... 120 seconds 

Ambient temperature range: 

housing 0° … +50°C / sensor -20° ... +90°C  

Transport and storage temperature:  -10 … +75 °C 
Relative air humidity: 

< 95 % 

Condensation: 

permitted (outside only)  

Overvoltage category (control unit): 

4000 V 

Degree of contamination: 

Material: 

Housing cover polycarbonate, housing base ABS, sensor  
cable PVC, cable screw connection PA6, sensor housing  
aluminium with polyamide PA6  

           

 

10. Dimensional drawing  

 
ELW 170: 

 

flange

 

 
 
 

Содержание ENGELAIR ELW 170

Страница 1: ...patents utility models or registered design The following warning notices are used in these instructions Immediate danger from electrical voltage and current Failure to heed the information indicated...

Страница 2: ...re not qualified The manufacturer s guarantee also ceases to apply in such instances 3 Standards and directives The device complies with the following requirements 2014 30 EU EMC directive 2014 35 EU...

Страница 3: ...e matched to one another according to the standards and specifications applicable locally The 2x2 pin terminal block for the rated voltage and the two 3 pin terminal blocks for the potential free rela...

Страница 4: ...and inductions The maximum permitted sensor cable length is 30 m Ensure that the four cables are connected correctly so that the Sensor or control electronics are not damaged 6 2 3 Connecting the swit...

Страница 5: ...s Factory setting 15 seconds 7 2 2 Switch off delay speed controller Allows the switch off delay to be set to between 2 and 20 seconds Factory setting 2 seconds 7 2 3 Hysteresis speed controller Allow...

Страница 6: ...e 100 240V AC or 24V 10 AC DC Rated consumption 3 VA Contact 2 two way contacts potential free Switching voltage max 250 V AC Switching current max 8 A Electric connection 2 5 mm sensor 1 0 mm screw t...

Страница 7: ...t The device should be stored in line with the ambient conditions specified in the technical data 13 Disposal When disposing of device be sure to separate the materials and recycle the device componen...

Отзывы: