background image

Gateway component ModbusTCP

3 / 30

1 General Information

1.1 Disclaimer

© 2019 KUNBUS GmbH, Denkendorf (Deutschland)

The contents of this user manual have been compiled by KUNBUS
GmbH with the greatest possible care. Due to technical
developments, KUNBUS GmbH reserves the right to change or
exchange the contents of this user manual without prior notice. You
can always obtain the latest version of the user manual from our
homepage: www.kunbus.com

KUNBUS GmbH shall be liable exclusively to the extent specified in
the General Terms and Conditions (www.kunbus.de/agb.html).

The contents published in this user manual are protected by
copyright. Reproduction or use is permitted for the internal use of the
user. Duplication or use for other purposes is not permitted without
the express written consent of KUNBUS GmbH. Contraventions will
result in damages.

Trademark protection

– KUNBUS is a registered trademark of KUNBUS GmbH.

– Windows® und Microsoft® are registered trademark of Microsoft, Corp.

KUNBUS GmbH
Heerweg 15 c
73770 Denkendorf
Germany

www.kunbus.de

1.2 Notes Regarding this User Manual

This user manual provides important technical information that can
enable you as a user to integrate the Gateway into your applications
and systems efficiently, safely and conveniently. It is intended for
trained, qualified personnel, whose sound knowledge in the field of
electronic circuits and expertise of Modbus TCP  is assumed.

As an integral part of the module, the information provided here
should be kept and made available to the user.

General Information

Содержание PR100088

Страница 1: ...User manual Gateway component Modbus TCP PR100088 1 17 2019 ...

Страница 2: ... Elements 8 3 3 Status LEDs 11 4 Installation 12 4 1 Preparations for Trouble free Operation 12 4 2 Requirements 14 4 3 Connecting Gateway Components 15 4 4 Installing a Gateway in the Control Cabinet 16 4 5 Connecting a Power Supply 17 4 6 Connecting a Gateway to the Fieldbus 18 5 Configuration 19 5 1 Supported size of Process Data 19 5 2 Address Assignment 19 5 3 Configure Modbus TCP 20 6 Integr...

Страница 3: ...or the internal use of the user Duplication or use for other purposes is not permitted without the express written consent of KUNBUS GmbH Contraventions will result in damages Trademark protection KUNBUS is a registered trademark of KUNBUS GmbH Windows und Microsoft are registered trademark of Microsoft Corp KUNBUS GmbH Heerweg 15 c 73770 Denkendorf Germany www kunbus de 1 2 Notes Regarding this U...

Страница 4: ...uct has been used incorrectly damage is due to non observance of the operating manual damage is caused by inadequately qualified personnel damage is caused by technical modification to the product e g soldering 1 5 Customer Service If you have any questions or suggestions concerning this product please do not hesitate to contact us KUNBUS GmbH Heerweg 15 C 73770 Denkendorf Germany 49 0 711 3409 70...

Страница 5: ...d electronic circuits basic knowledge of Modbus TCP work in electrostatic protected areas locally applicable rules and regulations for occupational safety 2 2 Symbols The symbols used have the following meaning DANGER Danger Always observe this information There is a safety hazard that can lead to serious injuries and death CAUTION Caution There is a safety hazard that can result in minor injuries...

Страница 6: ...he Internet is allowed Immediately change the default password for the web server You can find out how to do this in the chapter Changing the password Select a secure new password Check our website regularly for the latest software security alerts and updates for your product Install the security updates provided by us If you do not follow these instructions it is possible that your module data ma...

Страница 7: ...that master one specific protocol each You can combine these gateway components as you wish This design offers you a high degree of flexibility since you can exchange the individual gateway components at any time The following gateway components are currently available as slaves CANopen DeviceNet EtherCAT EtherNet IP Modbus RTU Modbus TCP POWERLINK PROFIBUS PROFINET Sercos III The gateway componen...

Страница 8: ...ponents with the RevPi Core 3 2 Control Elements Front view 1 2 3 Illustration 2 Front view 1 Status LEDs 2 Coding switch 8 pin DIP switch for setting the IP address 3 Fieldbus connection RJ45 socket for the connection to the fieldbus 2 sockets in all s figure top view Overview ...

Страница 9: ...w 1 Fieldbus connection RJ45 socket for the connection to the fieldbus total 2 pieces see picture front view 2 Interconnect ports for connecting the gateway components to each other 3 Locking clamp for secure fastening of the gateway component on the top hat rail Overview ...

Страница 10: ...teway component ModbusTCP 10 30 Bottom view 1 2 Illustration 4 Bottom view 1 Power supply with 24 V supply voltage 2 Locking clamp for secure mounting of the gateway component on the top hat rail Overview ...

Страница 11: ...ay component missing on red Serious error defect in the gateway MS off Gateway component is not running blinks green Configuration not completed on green Operation gateway component runs without errors NS off Gateway component is not running blinks green Standby mode no data exchange via Modbus TCP on green Connection is established data is ex changed L A 1 2 off No connection green Connection to ...

Страница 12: ...Line A Data and power supply lines for DC voltage below 60 V AC voltage below 25 V B Data and power supply lines for DC voltage between 60 V and 400 V AC voltage between 25 and 400 V C Power supply lines above 400 V You can route cables of the same group together in cable ducts or bundles Cables of group A and B Route the groups in separate bundles or in cable ducts at a minimum distance of 10 cm ...

Страница 13: ...otential equalization cables of up to 200 m in length 25 mm2 for potential equalization cables of more than 200 m in length Use potential equalization cables made of copper or galvanized steel Connect potential equalization cables extensively with the earth rail The smallest surfaces possible should be sandwiched between potential equalization cables and signal cables If the devices of the control...

Страница 14: ...is at a sufficient distance from other devices NOTICE Your gateway could be damaged if temperatures are too high èMake sure that the ambient temperature in the control cabinet is less than 60 C èKeep the ventilation slots unobstructed These must not be covered by cables etc èMaintain sufficient distance from other devices Illustration 5 Distances for installation Connect each gateway component ind...

Страница 15: ...way components Connect an interconnect port to each gateway component using the plug in jumper provided Illustration 6 Connecting gateway components ð You can now install the gateway in the control cabinet NOTICE Only ever interconnect 2 gateway components If you connect additional components severe defects could result on all devices Installation ...

Страница 16: ...30 4 4 Installing a Gateway in the Control Cabinet Hold the raster element of the gateway on the DIN rail Press down the locking elements towards the gateway Make sure that the gateway is firmly attached to the DIN rail Installation ...

Страница 17: ...t the functional earth with low impedance to the potential equalization You can then dispense with this connection if the shield of the fieldbus cable is connected to the potential equalization with lower impedance when entering the control cabinet NOTICE Connect each of the two gateway components to the power supply èEnsure in particular that no potential differences occur between the GND pins 2 ...

Страница 18: ...component ModbusTCP 18 30 4 6 Connecting a Gateway to the Fieldbus To connect the gateway component to Modbus TCP you need Two RJ45 connectors The pin assignment complies with the Ethernet standard Installation ...

Страница 19: ...Open the website http 192 168 0 X Log in Login data for initial logon User Admin Password 1701 Click on the Change Configuration button Set the desired IP address Confirm the entry with the Apply button Set all address switches to 0 Restart the gateway component by switching it off and on again ð The set IP address is now used Get IP address from DHCP server Set the value 255 all switches in the d...

Страница 20: ...mponent established 4098 0x1002 Fieldbus status of the other gateway com ponent Read Only Holding 0x00 Fieldbus not connected Make check all connections 0x01 Fieldbus connected no data communication Check whether an IP address is set 0x02 Gateway component configured no data communication 0x03 Cyclic data exchange 4099 0x1003 IP address Read Write Holding IP address High Word 4100 0x1004 IP addres...

Страница 21: ...alues that the other gateway compo nent supplies 16385 20224 Output Bits Coil Read Write Holding Values that are supplied to the other gateway component Input and Holding Register are not differentiated They can be read using function code 0x004 Functions You can access the data area of the gateway component using the following functions Function code Use Description Max size per telegram 0x01 Rea...

Страница 22: ...2 Web server files The files for the web server can be found in the subfolder Web 6 2 Webserver The Gateway has a web server You can access it from any browser Access web server Verbinden Sie das Gateway mit dem PC Open your browser Enter the IP address as URI e g http 192 168 0 8 ð You can log in now Log on to web server You can log on to the web server as an administrator or as a user The user c...

Страница 23: ...vel you have to enter a positive integer If this is at least 2 then the user is an administrator Example for a password xml xml version 1 0 encoding UTF 8 Passwords User0 NutzerEins User0 Password0 93h31m Password0 Level0 1 Level0 User1 NutzerZwei User1 Password1 53cr3t Password1 Level1 3 Level1 Passwords Tip As admin you can change the password directly in the web server Display process data The ...

Страница 24: ...ditions ü Your gateway is on your network ü The network interface is correctly configured ü You have installed an FTP program on your PC Open your FTP program Click on New connection destination Enter the following values Transmission protocol FTP Computer name IP address of the gateway compo nent The following address is used on de livery 192 168 0 8 Port number 21 User name Username for the web ...

Страница 25: ...ata security we rec ommend that you change your pass word as quickly as possible and do not continue to use the stored val ues You can change your password via the web server Safe You can optionally save these set tings This allows you to access the gateway component more quickly via FTP in the future Click on Login Integrated servers ...

Страница 26: ... ModbusTCP 26 30 Select in the kfu file from your local resources window 1 Drag and drop the kfu file into the root directory of your gateway component window 2 The following window opens Click on ok Integrated servers ...

Страница 27: ...teway component ModbusTCP 27 30 The update file will now be copied After successful copying the file appears in the root directory of the gateway component Restart the gateway component Integrated servers ...

Страница 28: ...Gateway component ModbusTCP 28 30 Log on to the web server Here you can check whether the software version has changed Integrated servers ...

Страница 29: ...y 24 V DC Power consumption during operation cyclical data exchange 100 mA Status display LED Environmental conditions Ambient temperature 0 60 C Storage temperature 25 60 C Humidity 93 at 40 C Condensing Not allowed Protection class Control cabinet Housing Terminal area IP54 IP20 IP20 Assembly data DIN rail 35 x 7 5 mm Height 96 mm Depth 110 4 mm Technical Data ...

Страница 30: ...Gateway component ModbusTCP 30 30 Illustration 7 Side dimensions Illustration 8 Front dimensions Technical Data ...

Отзывы: