User Manual

Gateway component for EtherNet/IP

PR100066 • 1/7/2016

Содержание PR100066

Страница 1: ...User Manual Gateway component for EtherNet IP PR100066 1 7 2016...

Страница 2: ...ality 6 3 2 Control Elements 8 3 3 Status LEDs 11 4 Installation 12 4 1 Preparations for Trouble free Operation 12 4 2 Requirements 14 4 3 Connecting Gateway Components 15 4 4 Installing a Gateway in...

Страница 3: ...shall be liable exclusively to the extent specified in General Terms and Conditions www kunbus de agb html The contents published in this user manual are protected by copyright Any reproduction or use...

Страница 4: ...kept and made available to the user 1 3 Validity This document describes the application of the KUNBUS Gateway with the product number PR100066 release 00 1 4 Limitation of Liability Warranty and lia...

Страница 5: ...med electronic circuits basic knowledge of EtherNet IP work in electrostatic protected areas locally applicable rules and regulations for occupational safety 2 2 Symbols The symbols used have the foll...

Страница 6: ...s of 2 gateway components that master one specific protocol each You can combine these gateway components as you wish This design offers you a high degree of flexibility since you can exchange the ind...

Страница 7: ...gateway component enables communication with Ethernet IP and Modbus TCP It supports the following functions RPI Minimal Requested Packet Interval 1 ms ACD Address Conflict Detection DLR You can use t...

Страница 8: ...ntrol Elements Front view 1 2 3 Illustration 2 Front view 1 Status LEDs 2 Coding switch 8 pin DIP switch for setting the IP address 3 Fieldbus connection RJ45 socket for the connection to the fieldbus...

Страница 9: ...ation 3 Top 1 Fieldbus connection RJ45 socket for connection to the fieldbus 2 pcs see figure front view 2 Interconnect ports for interconnecting the gateway components 3 Locking clamps for securely a...

Страница 10: ...ateway component for EtherNet_IP 10 25 Bottom 1 2 Illustration 4 Bottom 1 Mains connection with 24 V power supply 2 Locking clamps for securely attaching the gateway component to the DIN rail Overview...

Страница 11: ...way component operational blinks green Configuration not completed on red Unrecoverable error flashes red Configuration error flashes red and green Self test NS off Gateway component is switched off o...

Страница 12: ...rom any unintended electromagnetic interferences The following groups should be routed separately from each other Group Line A Data and power supply lines for DC voltage below 60 V AC voltage below 25...

Страница 13: ...pedance Select the following as a reference value for the cross section of the potential equalization cable 16 mm2 for potential equalization cables of up to 200 m in length 25 mm2 for potential equal...

Страница 14: ...y is at a sufficient distance from other devices NOTICE Your gateway could be damaged if temperatures are too high Make sure that the ambient temperature in the control cabinet is less than 60 C Keep...

Страница 15: ...components Connect an interconnect port to each gateway component using the plug in jumper product number PR100204 Illustration 6 Connecting gateway components You can now install the gateway in the c...

Страница 16: ...6 25 4 4 Installing a Gateway in the Control Cabinet Hold the raster element of the gateway on the DIN rail Press down the locking elements towards the gateway Make sure that the gateway is firmly att...

Страница 17: ...t the functional earth with low impedance to the potential equalization You can then dispense with this connection if the shield of the fieldbus cable is connected to the potential equalization with l...

Страница 18: ...nent for EtherNet_IP 18 25 4 6 Connecting a Gateway to the Fieldbus To connect the gateway component to EtherNet IP you need Two RJ45 connectors The pin assignment complies with the Ethernet standard...

Страница 19: ...es Input Only Output master slave 254 0 bytes Input slave master 150 up to 480 bytes Listen Only Output master slave 255 0 bytes Input slave master 150 up to 480 bytes NOTICE Bear in mind that the max...

Страница 20: ...equired Confirm your entry by pressing the Apply button Set all address switches to 0 Restart the gateway component by switching this off and then on again The set IP address is now used Receiving IP...

Страница 21: ...details about the implemented attributes from the EDS file provided Device Specific Objects The following objects are device specific You can use these to access the input and output data acyclically...

Страница 22: ...registers Register The following registers are implemented in the gateway component Address area Function Access 1 240 Input register receives values of the partner gateway component Read only 1025 12...

Страница 23: ...same memory cell however No separate address areas is defined for the input register Read the holding register with function code 0x04 Register area for bit by bit access coils You can also access the...

Страница 24: ...ply 24 V DC Power consumption during operation cyclical data exchange 100 mA Status display LED Environmental conditions Ambient temperature 0 60 C Storage temperature 25 60 C Humidity 93 at 40 C Cond...

Страница 25: ...Gateway component for EtherNet_IP 25 25 Illustration 7 Side dimensions Illustration 8 Front dimensions Technical Data...