background image

CONTENTS 

 
 

Section 1– Stove placement, air requirements, and clearances…..  pg. 1-2 

 
 

 

  2– The flue and flue connections………………………… pg. 2-3 

 
 

 

  3– Fuel tank installation and fuel line connections………. pg. 3-4 

 
 

 

  4– Lighting, adjustments to carburetor, and draft 

 

 

          stabilizer adjustments………………………………. pg. 4-7 

 
 

 

  5– Servicing……………………………………………..  pg. 7-8 

 
 

 

  6– Trouble-shooting guide……………………………..... pg. 8-10 

 
 

 

  7– Warranty……………………………………………… pg. 10 

 
 
 

SECTION 1 

Stove placement, air requirements, and clearances 

 
 

Try to pick a location that will be somewhat central in the house or room in which you 

wish to install the Oil Classic.  Due consideration of the fuel tank location, ease of fuel line 
installation, and flue location is wise.  You will want to read the fuel tank section to get a better 
idea of where to locate the tank as well as the stove.  The stove must be placed on hearth that is 
non-combustible, having a thickness of 3/8” or greater.  A 36”x 36” hearth pad area is 
recommended.  Once a location is established, the stove can be placed on the hearth and 
leveled.  It is absolutely imperative that your Oil Classic is level.  There are adjustment bolts 
under each corner of the pedestal base should these adjustments be necessary.  Place a level on 
top of the pedestal base both directions and adjust until level. 
 

This unit has been tested to U.L. 307A and is approved for installation and use in 

manufactured homes.  There are some special considerations when installing into a mobile or 
manufactured home.  For  model OC-10 (10” burner), the flue system must consist of a 6” 
diameter CLASS “A”, U.L. HT103 type insulated chimney, and a double-wall stove pipe 
connector.  For models OC-7 and OC-8 (7” and 8” burner), a 4”, 5”, or 6”diameter chimney 
may be used, but must be Class “A” insulated chimney or approved 4” diameter Class 
“L” (pellet vent) chimney.  Dura-Vent D.V.L. double-wall connector with a Dura-Vent # 8680 
double-wall adapter is required or 4” diameter Class “L” vent may be used as a connector.  The 
manufactured homeinstallation also requires an outside combustion air source.  If outside air is 
accessed through the floor, a 4” diameter or larger duct should be installed through the hearth 
and floor, extending past the insulation barrier on the underneath side of the home.  Make sure 
there is a rodent screen with a maximum 1/4” x 1/4” opening placed over the duct opening to 
prevent rodents from accessing the stove bottom.  

Содержание OC-10

Страница 1: ...ove it is recommended that the installation be done by a qualified installer familiar with fuel oil stoves preferably an NFI Certified National Fireplace Institute expert We recommend contacting local building or fire officials in your area regarding restrictions and installation inspection requirements Please read this entire manual before attempting installation or operation of this appliance Im...

Страница 2: ...orner of the pedestal base should these adjustments be necessary Place a level on top of the pedestal base both directions and adjust until level This unit has been tested to U L 307A and is approved for installation and use in manufactured homes There are some special considerations when installing into a mobile or manufactured home For model OC 10 10 burner the flue system must consist of a 6 di...

Страница 3: ...t will make the combustion impervious to house pressure problems Please note that these clearances are minimums It is a good idea to exceed these clearances unless space is limited Common sense must prevail Minimum Clearances to Combustibles Sides Back Flue Pipe Corner Top Standard 8 6 9 4 Alcove 8 6 9 4 54 Note Corner clearance applies only when the stove is installed in a room corner with the st...

Страница 4: ... must be removed and the draft stabilizer adjusted Its purpose is to allow more or less air to travel into the flue to compensate for a change in the flue draft Adjustment of the draft stabilizer will be discussed in Section 4 SECTION 3 Fuel tank installation and fuel line connections OIL Your Kuma Oil Classic comes with a carburetor set for an average of a 2 35 cc viscosity rating You should be a...

Страница 5: ...g carburetor adjustments and draft stabilizer adjustments PRE LIGHTING CHECKS The installation should be inspected to ensure that the work is complete and the workmanship is satisfactory No stove should be lit if any part of the installation does not comply with the relevant standards and regulations The oil tank should be examined to confirm there is a supply of the correct grade of oil that a fi...

Страница 6: ...r should begin burning blue at flame base and yellow at flame tip At this point a pressure check should be made and the draft stabilizer adjusted to within the recommended pressure setting range see draft pressure chart on page 7 8 Run the stove for at least 30 minutes on low or medium to allow the whole stove and chimney to come up to operation temperature 9 Turn the control knob to setting 1 and...

Страница 7: ...tes before re starting following the lighting instructions in this manual If you have any questions about the operation of your Oil Classic please check the trouble shooting section of this manual or call your dealer DRAFT STABILIZER ADJUSTMENTS After removing the rear draft stabilizer access cover the 7 x 7 square cover in the middle of the stove back you will see that the draft stabilizer has a ...

Страница 8: ... stove interior and drip pan Lightly brush off catalyst and inspect for deterioration replace if necessary Check all gaskets rope seal around door window seal check for loose glass no need to remove access panel gaskets Check oil tank for damage or leaks and clean or replace main tank filter Check all lines and connections for leaks or deterioration A draft reading should be taken for low and high...

Страница 9: ... near fuel inlet SECTION 6 Trouble shooting guide CONDITION 1 Oil present in burner with the carburetor in off position 2 No oil in burner bottom after carburetor is turned on 3 Flame smoky when lit 4 Flame smoky when burning low 5 Flame smoky when burning high 6 Flame goes out on low 7 Flame goes out in high winds 8 Burner goes out and will not re light 9 Flame is noisy buzzing or roaring or sepa...

Страница 10: ...d draft stabilizer may need to be installed in the pipe as well to compensate A wind directional cap or vacuum cap may be helpful to prevent wind gusts and down drafts from affecting pressure 8 No oil in tank Valve in fuel supply line shut inadvertently Fuel supply blocked plugged filter frozen water Carburetor on off lever tripped 9 Stove door having been open for a while and then shut a roaring ...

Страница 11: ...l line supplied with stove 2 years Warranty does not cover gold plated door surface normal maintenance items such as paint glass and gasket This warranty does not apply in cases of abuse mishandling unauthorized repair alterations failures or operating difficulties due to misuse accident misapplication improper installation improper maintenance or service Kuma Stoves reserves the right under this ...

Отзывы: