9.5. 

Sprinkler operation 

The following functions are intended for the operation of an electrical sprinkler pump: 

  Switching of all shutdown alarms (overspeed alarm remains switched off for electronic speed sen-

sor, demand VDS 2100-22) to warning 
Optionally, the inhibition of the generator switch-off function for 

GENERATOR OVERCURRENT

, for ex-

ample  

  Start program to 6 (parameterisable) start attempts 

  Upon sprinkler request being withdrawn: Cessation of the sprinkler operation after the 

SPRINKLER 

IDLE TIME

, or only manual switching off 

  for the duration of the acceleration time of the sprinkler pump: Switching off of the normal consum-

ers or no interruption. 

 
The supply of the sprinkler pumps is usually taken care of directly by the generator and thus prior to 
the switch to the emergency power consumers. If a sprinkler request is arises, the genset starts. In the 
event of an additional request from the remote start command, the consumers can be switched off for 
a parameterisable period of time in order for enough energy to be available to allow the sprinkler pump 
to start up. Furthermore, it is possible to parameterise that the consumer switches remain switched on 
or switch off in the event of an overload on the side of the consumers. 
Sprinkler operation is automatically cancelled after the sprinkler requirement is removed after an en-
tered idle time or can only be ended manually (demand VDS 2100-22).

 

If the automatic system is pa-

rameterised for manual shutdown, the LED of the O

FF 

operating mode flashes as soon as the sprinkler 

input is free. Stopping can then be carried out via the O

FF 

operating mode (or always via Emergency 

Stop). 

10. 

Error messages / Programmable operation indicators 

Any of the 10 LEDs can either display an error message or be parameterised as an operation indica-
tors. 

10.1. 

Use as an operational indicator 

These displays are independent of the selected operating mode. Thus, they can be used as displays 
of operational conditions via contact inputs as normal signal lamps. The parameterisation is described 
in the service instructions. 

10.2. 

Use as an error message 

The arrival of an error message is displayed by the LED flashing. At the same time, the acoustic signal 
(for the entered duration) is controlled. The acoustic signal is switched off with a pulse from the A

LARM 

O

FF 

key (or automatically after the entered time). However, the LED continues to flash. If the value 0 

sec. is entered for the duration of the horn switch-on, no automatic switch-off is carried out: The horn 
remains switched on until manually deleted. 
Due to a second button actuation of A

LARM 

O

FF

, the message switches from flashing to continuously il-

luminated. Due to the necessary second acknowledgement, e.g. the switching off of the acoustic sig-
nal generator after an automatic switch-off, it can be distinguished which error message has newly oc-
curred. 
The display is cleared after the error is eliminated after renewed actuation of the A

LARM 

O

FF 

key. 

With messages that lead to the switching-off of the genset, further operation is inhibited and this is in-
dicated  by 

AUTOMATIC  SYSTEM  LOCKED

.  In order  to unlock,  the  O

FF 

operating  mode  (any  actuated  ex-

ternal Emergency OFF buttons must also be unlocked) must be

 

selected. 

If the generator is switched off due to a warning alarm in automatic operation, the engine is stopped after the idle 
time and the automatic system is locked. 
The parameterisation is described in the service instructions. 

10.3. 

Alarms 9 and 10 

Both these alarms can be delayed from 0 to 240 sec. by the signal transmission, i.e. for the alarm con-
tact  to  issue  an  error,  the  signal  must  be  pending  for  a  parametrised  time.  Furthermore,  both  these 
alarms are also effective in the Off operating mode (Off), but without switching on the horn. Thus, crite-
ria (e.g. tank overfilling, leakage warning) that always have to be reported can be monitored.  
 

Содержание KEA 292 INS

Страница 1: ...d the parameters can be set with a PC Because the KEA 292 has the same dimensions and fastenings as its predecessor replacement is simple Ten parameterisable alarm and operating indicators which can b...

Страница 2: ...9 5 Sprinkler operation 7 10 Error messages Programmable operation indicators 7 10 1 Use as an operational indicator 7 10 2 Use as an error message 7 10 3 Alarms 9 and 10 7 10 4 Internal error message...

Страница 3: ...set via a USB inter face The PARAWIN software is required for this All relevant values and signals can be read out via an add on module The device is delivered with standard parameterisation and labe...

Страница 4: ...w can be selected using the keys 7 2 Start key The motor can be started in MANUALoperating mode by actuating this button If the motor needs to be preheated the pre heating device must be externally co...

Страница 5: ...out as soon as the genset exceeds the ignition speed during start up recognised through the D signal of the generator through the speed sensor signal or through the generator voltage in accord ance w...

Страница 6: ...be select ed 9 3 Auto operating mode After the external start command is present the genset will be started after the parameterised delay time has elapsed The START CONTROL indication flashes as long...

Страница 7: ...of the 10 LEDs can either display an error message or be parameterised as an operation indica tors 10 1 Use as an operational indicator These displays are independent of the selected operating mode T...

Страница 8: ...et can immediately switch to generator operation in the event of a start request sprinkler request 10 4 5 Generator circuit breaker tripped The alarm is internally controlled if no generator feedback...

Страница 9: ...display remains switched on 14 Start program 14 1 Start process diesel engine 1 Start delay 2 sec 2 Starter on for 10 sec 3 Pause 7 sec 4 3 start attempts 5 6 start attempts for sprinkler operation 6...

Страница 10: ...puts 2 phase generator voltage monitor for nominal voltage 400 V adjustable in 1 Volt steps Adjustable 250 480 Volt Generator frequency 45 to 65 Hz adjustable in 0 01 Hz steps from 40 to 70 Hz Battery...

Страница 11: ..._______________________________________________________________________________ Alfred Kuhse GmbH Telephone 49 4171 798 0 kuhse kuhse de Subject to technical changes An der Kleinbahn 39 D 21423 Winsen...

Страница 12: ...INS_EN_Ver 2016 07 01 doc 12 Alfred Kuhse GmbH Telephone 49 4171 798 0 E mail kuhse kuhse de Subject to technical changes An der Kleinbahn 39 21423 Winsen Fax 49 0 4171 798 117 http www kuhse de 16 2...

Страница 13: ...___________________________________________________________________________ _____ Alfred Kuhse GmbH Telephone 49 4171 798 0 kuhse kuhse de Subject to technical changes An der Kleinbahn 39 D 21423 Wins...

Отзывы: