7
Mounting steps
(see fig. 1)
• Clean mounting surface (1) carefully.
• Remove protective foil (2) from the adhe-
sive side of the magnetic strip (3).
• Stick down the magnetic strip (4).
• Clean surface of magnetic strip carefully.
• Remove protective foil (6) from adhesive
tape on the cover strip (5).
• Fix cover strip (both ends should slightly
overlap).
• Also fix cover strip’s ends to avoid uninten-
tional peeling.
Fig. 1 mounting of the magnetic strip
Mounting examples
Mounting with chamfered ends (fig. 2) is not
recommended unless the strip is installed in a
safe and protected place without environmen-
tal influences. In less protected mounting pla-
ces the strip may peel. There we recommend
mounting accord. to fig. 3 and 4.
Mounting in a groove (fig. 5) best protects the
magnetic strip. The groove should be deep
enough to totally embed the magnetic strip.
Attention
:
Do not expose the system to magnetic fields.
Any direct contact of the magnetic strip with
magnetic fields (eg. adhesive magnets or other
permanent magnets) is to be avoided. Sensor
movements during power loss are not captured
by the follower electronics.
Fig. 2
Fig. 3
Fig. 5
Fig. 4
3.3 Mounting of the magnetic sensor
L
LIIM
ME
ES
S
L1 and L2
The magnetic sensors
LIMES L1 and L2
can be
fastened by using two bolts M3 over the ø3.5 mm
through holes.
Cables should be layed in such a way that there
is no danger of damaging. Provide ten-sion relief
and drag chain or casing, if neces-sary.
Observe the correct alignment with regard to
the counting direction
(Figs.6).
Attention!
The tolerance and gap measures must
be observed over the whole measuring length.
Mounting magnetic senosr/magnetic strip
4. Electrical connection
• Wiring must only be carried out with power off!
• Check all lines and connections before swit-
ching on the equipment!
Interference and distortion
All connections are protected against the effects
of interference.
The location should be selected
to ensure that no capacitive or inductive inter-
ferences can affect the sensor or the connec-
tion lines!
Suitable wiring layout and choice of
0,1 ... 2 mm
sensor– magnetic
strip
< 3°
< 1°
< 3°
±1 mm