![Kübler 573T Скачать руководство пользователя страница 46](http://html.mh-extra.com/html/kubler-0/573t/573t_operating-manual_2008461046.webp)
R60726.0002
–
Index 6b
EN - page 46
6.2
Modbus RTU Interface
The Modbus
interface of the 57xT series is a standard Modbus RTU Slave and provides
the following Modbus functions:
•
Read Coils
•
Write Single Coil
•
Read Holding Registers
•
Write Multiple Registers
•
Diagnosis
For the operation of the interface module and the understanding of this manual basic
knowledge in Modbus RTU communication is presupposed.
6.2.1
Parameter setting
Required parameter settings in 6.571T.XXX.X0X / 6.571T.XXX.XAX
“Serial menu”:
UNIT NUMMER
Not valid for Modbus communication
(For setting of Modbus address see parameter “MODBUS”)
SERIAL BAUD RATE
This parameter defines the serial baud rate
0
9600
9600 baud
1
19200
19200 baud
2
38400
38400 baud
SERIAL FORMAT
This parameter defines the bit data format.
0
7-EVEN-1
Do not use with Modbus protocol
1
7-EVEN-2
2
7-ODD-1
3
7-ODD-2
4
7-NONE-1
5
7-NONE-2
6
8-EVEN-1
8 data bits Parity even 1 stop bit
7
8-ODD-1
8 data bits Parity odd 1 stop bit
8
8-NONE-1
Do not use with Modbus protocol
9
8-NONE-2
8 data bits no Parity 2 stop bits