8.2.4 Media: For data sources come from 2 Serial ports (Serial 1 ~ 2) and 4 remote TCP devices
(Socket 1 ~4). .
8.2.5 Endial: Endianness
8.2.6 Slave: Input ID of Modbus Slave. Different Modbus Devices on the same “Media” must not
repeat ID.
8.2.7 REG.Start: register address.
1 – 9999
: Read/Writeable Coils
(modbus function code 0x01)
10001-19999 : Read only Coils
(modbus function code 0x02)
30001-39999 : Read only Registers
(modbus function code 0x04)
40001-49999 : Read/Writeable Registers (modbus function code 0x03)
* Please check Modbus device whether register start from 0 or 1.