TAMPER ANALYSIS
When the sensor is switched on, the MEMS system is calibrated for the
acquired position, when 3-4 degrees shifts occur, it generates an alarm on
the tamper output (T-T). Immediately after a movement detection, the
accelerometer re-calibrates to the current position.
INHIBITION SYSTEM STATUS INPUT
• For inhibition system status, power supply 12V to input “I”.
• Passing from 12V to 0V (it enables the use of the LED), the detector
calibrates if there is an anti-mask and/or accelerometer memory.
• Input “I” has priority with respect to DIP-SWITCH 1.
FAULT / MASKING OUTPUT
• When a "Fault / Masking" occurs, output "F" is enabled.
• In case of Masking, besides the activation of output "F", the status LED
will also flash.
• In the case of Ksenia End of Line (EoL) resistors, the fault is signaled
with the relative balancing.
WALK TEST
The Walk test procedure starts immediately after the heating / calibration
time, and it lasts for maximum 10 minutes.
During this time it’s possible to test the coverage of microwave and
infrared, using the RGB LED. Please refer to previous table for
understand the meaning of LED colors.
Note
: during the Walk test, the LED is always enabled (regardless the DIP
SWITCH / “I” input settings).