5 Installation at Site
23 of 44
UPAchrom
1
2
3
4
Fig. 5:
Cable clip
1
Flat cable
2
Riser
3
Plastic stud
4
Rubber strap
5.3 Installing the pump set in a horizontal position
WARNING
Persons could fall into unsecured wells/reservoirs/tanks
Risk of personal injury!
▷
During installation work, take suitable precautions to protect anyone from
falling into an open well/reservoir/tank.
▷
Suitably fence off the work area.
WARNING
Installation on mounting surface which is unsecured and cannot support the load
Personal injury and damage to property!
▷
Use a concrete of compressive strength class C12/15 which meets the
requirements of exposure class XC1 to EN 206-1.
▷
The mounting surface must have set and must be completely horizontal and
even.
▷
Observe the weights indicated.
CAUTION
Temperature and pressure increase of the motor fill
Damage to the motor!
▷
Always protect non-flooded pump sets against direct exposure to sun.