BOAX
--S
9
BOAXMAT
--S -- Valve with electric actuation
Main electrical equipments
ACTELEC
OA 3
OA 6
OA 8
OA 15
AS 25
AS 50
BS 100
Opening and closing
limit switches
Standard
Adjustable extreme position
mechanical stops
Standard
Opening and closing
torque limit switches
Standard
Thermic switch integrated
in the winding
Standard
Manual override
Standard
Mechanical limit switch position
Standard
Electrical characteristics (for standard operating time)
ACTELEC
Single phase A. C. 230 V, 50 Hz
ACTELEC
OA3
OA6
OA8
OA15
AS25
AS50
BS100
Nominal intensity (A)
0,7
0,6
1,2
0,6
1,8
1,2
1,2
Starting intensity (A)
0,9
0,9
1,7
0,9
2,5
1,7
1,7
Power (W)
27
30
60
30
100
60
60
ACTELEC type
3--phase A. C. 400 V, 50 Hz
ACTELEC type
OA 6
OA 8
OA 15
AS 25
AS 50
BS 100
Nominal intensity (A)
0,3
0,6
0,3
0,8
0,3
0,6
Starting intensity (A)
0,5
1,1
0,5
1,6
0,8
1,1
Power (W)
30
100
30
150
60
100
•
Rated current:
-- single phase A. C.230 V, 50 Hz: all types,
-- 3--phase A. C. 400 V, 50 Hz: all types except OA 3
•
Intermittent duty:
-- S4--20 % for OA 3,
-- S4--30 % for OA 6 to BS 100
•
Protection degree: IP 67
•
Working temperature from -- 20
°
C to + 70
°
C
•
On request:
-- Explosion--proof protection,
-- Additional adjustable contacts,
-- Electrical motor with built--in thermal protection and
epoxy paint finish,
-- Regulation function,
-- Feed--back position,
-- Potentiometer,
-- Control boxes,
-- Other voltages.
Please consult us.
Содержание BOAX-S
Страница 14: ...BOAX S 14 Notes...
Страница 15: ...BOAX S 15 Notes...