8 Trouble-shooting
23 of 32
Ama-Drainer N 301/302/303/358
8 Trouble-shooting
WARNING
Improper work to remedy faults
Risk of injury!
▷
For any work performed to remedy faults, observe the relevant information
given in this operating manual and/or in the product literature provided by the
accessories manufacturer.
If problems occur that are not described in the following table, consultation with the
KSB
customer service is required.
Table 8:
Trouble-shooting
Trouble-shooting
Possible cause
Remedy
5)
Pump is running, but does not or
hardly deliver.
The hydraulic system is clogged by
foreign matter.
Clean the hydraulic system with a water
jet.
(
ð
Section 6.3, Page 18)
The discharge line is closed.
Open all accessories fitted at the
discharge line.
The lift check valve has been fitted for
the opposite direction of flow or is
clogged.
Reassemble observing the correct
sequence
(
ð
Section 9.1, Page 24)
or
clean the lift check valve.
The pump is not running or only
for a short time.
The thermal motor protection device
triggers because:
1) Pump overheating
Check the fluid temperature.
2) Pump running dry
Verify the minimum fluid level.
The power supply is interrupted
Check the electrical installation.
5)
Pump pressure must be released before attempting to remedy faults on parts which are subjected to pressure. Disconnect
the pump from the power supply and let it cool down.
Содержание Ama-Drainer N 301
Страница 1: ...Submersible Motor Pump Ama Drainer N 301 302 303 358 Installation Operating Manual ...
Страница 29: ......
Страница 30: ......
Страница 31: ......