ID.: 17-16-20-2976-06 | 6.2017
31
7.3 Settings for programmes and parameters
7.3.1 Setting the water temperature
Pressing the key
or
for the first time displays the currently set temperature, additionally
pressing the key
or
(in the time frame of 10 seconds) triggers its modification. If we wait
for 5 seconds, the new setting will be stored after the blinking stops.
7.3.2 Switching between various operation programmes
Switching between various operation programmes is performed by additionally pressing the
key
P
in the time frame of 8 seconds - this switches between available operational
programmes.
7.3.3 Display and settings of parameters
We enter the settings by pressing the key
and
at the same time. The parameter L.0 is
displayed. This enables us to choose the desired parameter by pressing the key
or
.
When the desired parameter has been chosen, we have to wait for 8 seconds, then the value
of the chosen parameter is displayed. During the display of the parameter the value of the
parameter can be changed with the key
or
. After the value has been chosen, we have
to wait 10 seconds to confirm the value of the parameter and the display returns to the basic
menu which displays the current water temp. in the buffer tank for DHW.
7.3.4 Programme “Antifreeze”
P.0
The operation of the device is turned off, only the temperature display in the buffer tank for
DHW is active. The programme “Antifreeze” is active, it maintains the water temperature in the
buffer tank for DHW at 10 °C.
7.3.5
Programme “Normal”
P.1
Basic
The device in the programme “Normal”
P.1
heats the water with the device’s generator until
the set temperature is reached and until the temperature of the evaporator is above min.
operating temperature (L.1). If the air in the room cools below the set operating temperature,
the device performs a security shut-down of the device’s generator. When the air temperature
in the room is above the minimal temperature at least for 60 minutes, the device activates the
device’s generator and continues heating the water up to the set temperature. Water
overheating in the programme “Normal” P.1 is performed with the device’s generator.
Renewed heating starts when the water temperature set with the standby value (L.4) drops
below the set desired temperature of the buffer for DHW.
7.3.6 Programme “Res. Source”
P.3
Basic
During the programme “Res. Source”
P.3
the device heats the water with the electric heater to
the set temperature independently form the evaporator temperature.
Advanced
The electric heater (EH) is active until the set water temperature is reached.
Renewed heating starts when the water temperature set with the standby value (L.4) drops
below the set desired temperature of the buffer for DHW.