46
9 Supplement
OPTISOUND 3030 C • Foundation Fieldbus
51118-EN-210701
•
CAL_POINT_LO
–
Min./max.-adjustment: Lower calibrated point of the sensor. It refers to 'Cal_level_lo'. The unit
is defined in 'Sensor_range.unit'
•
CAL_LEVEL_HI
–
Min./max.-adjustment: Level at 'Cal_point_hi'. When writing 'Cal_level_hi' and 'Cal_type' = 1
(Online) the 'Cal_point_hi' is automatically set to the current sensor value. The unit is defined in
'Level_unit'
•
CAL_LEVEL_LO
–
Min./max.-adjustment: Level at 'Cal_point_lo'. When writing 'Cal_level_lo' and 'Cal_type' = 1
(Online), the 'Cal_point_lo' is automatically set to the current sensor value. The unit is defined
in 'Level_unit'
•
CAL_TYPE
–
Min./max.-adjustment: Defines type of calibration: Dry: no influence of sensor value. Online:
current sensor value determines 'Cal_point_hi/lo'
•
level
–
Value after min./max. adjustment
•
level_unit
–
Unit code of 'Level', 'Level_offset', 'Cal_level_hi', 'Cal_level_lo'
•
level_offset
–
Offset that is added to the 'Level' value. Unit derives from 'Level_unit'
•
SENSOR_OFFSET
–
Offset that is added to the 'Sensor_value'. Unit derives from 'Sensor_range.unit'
•
end_of_operation_range
– Set up to suit the process conditions
•
begin_of_operation_range
– Set up to suit the process conditions
•
product_type
–
Set up to suit the process conditions. If Special-Parameter adjustment has been utilized this
parameter cannot be written
•
liquids_medium_type
–
Set up to suit the process conditions. If Special-Parameter adjustment has been utilized this
parameter cannot be written
•
solids_medium_type
–
Set up to suit the process conditions. If Special-Parameter adjustment has been utilized this
parameter cannot be written
•
liquids_vessel_type
–
Set up to suit the process conditions. If Special-Parameter adjustment has been utilized this
parameter cannot be written
•
solids_vessel_type
–
Set up to suit the process conditions. If Special-Parameter adjustment has been utilized this
parameter cannot be written
•
fast_level_change
–
Set up to suit the process conditions. If Special-Parameter adjustment has been utilized this
parameter cannot be written
•
first_echo_factor
– Set up to suit the process conditions
•
pulse_velocity_correction
– Set up to suit the process conditions
•
echo_quality
–
Signal/Noise ratio
•
empty_vessel_curve_corr_dist
– Distance from the sensor to the product surface. Unit derives from 'Sensor_range.unit'
•
empty_vessel_curve_corr_op_code
Содержание OPTISOUND 3030 C
Страница 1: ...OPTISOUND 3030 C Handbook Ultrasonic Level Transmitter Foundation Fieldbus ...
Страница 3: ...3 Contents OPTISOUND 3030 C Foundation Fieldbus 51118 EN 210701 Editing status 2019 03 12 ...
Страница 50: ...50 Notes OPTISOUND 3030 C Foundation Fieldbus 51118 EN 210701 ...
Страница 51: ...51 Notes OPTISOUND 3030 C Foundation Fieldbus 51118 EN 210701 ...