Checking the usage

Intended use

The gas pressure regulator VGBF serves to maintain 

a constant outlet pressure p

a

 despite changing gas 

flow rates and inlet pressures p

e

 in gas pipelines. 

This function is only guaranteed when used within 

the specified fields of application – see [Technical 
data – p. 5]. 

Any other use is considered as non-compliant.

Type code

Code

Description

VGBF

Gas pressure regulator

15 – 150

Nominal size

R
F

Rp internal thread

Flange to ISO 7005

05
10
40

p

e max.

 500 mbar

p

e max.

 1 bar 

p

e max.

 4 bar 

-1
-

Screw plug at the inlet

Screw plug at the inlet and outlet

L

 

 

For air only (without approval) 

Medium: aggressive gases (check 

suitability), rubber parts coming into 

contact with gas made of Viton  

(without approval)

Part designations

VGBF..F

VGBF..R

10

1

1

2

3

3

4

4

5

6

6

7

7

8

8

9

9

2

1

Cover cap and adjusting screw

2

Breather screw

Impulse line connection (not on VGBF..05)

4

Outlet

5

Outlet (p

a

) measuring connection

6

Arrow of direction of flow

7

Inlet (p

e

) measuring connection

8

Inlet

9

Type label

10

Damping valve for VGBF 40 – 100..40

Inlet pressure p

e

, outlet pressure p

a

 and ambient 

temperature: see type label.

Vor dem Öffnen Feder 

entspannen! 
Release spring 

before opening! 
Avant d'ouvrir le dôme, 

détendre le ressort! 

VGBF 
 

CE: 0063AQ0973 

Installation

 CAUTION

Please observe the following to ensure that the 
gas pressure regulator is not damaged during the 
installation:
Install the unit free of mechanical stress.
Sealing material, cuttings and other impurities must 
not be allowed to get into the regulator housing.

The installation location must be dry. Do not install 

the unit in the open air.
Installation in the vertical or horizontal position, 
never upside down.

The outlet pressure p

a

 is set at the factory with 

the spring dome pointing vertically upwards. If 
the VGBF is installed with the spring dome in the 
horizontal position, check and adjust the outlet 
pressure p

a

 (see [Changing the outlet pressure 

pa – p. 4]). 

  1 

Install a filter upstream of the unit, in order to 
protect it against impurities in the pipeline.

VGBF..F

>20

mm

4

2

3

5

VGBF..R

>20

mm

4

2

3

6

5