Checking the usage
Intended use
The gas pressure regulator VGBF serves to maintain
a constant outlet pressure p
a
despite changing gas
flow rates and inlet pressures p
e
in gas pipelines.
This function is only guaranteed when used within
the specified fields of application – see [Technical
data – p. 5].
Any other use is considered as non-compliant.
Type code
Code
Description
VGBF
Gas pressure regulator
15 – 150
Nominal size
R
F
Rp internal thread
Flange to ISO 7005
05
10
40
p
e max.
500 mbar
p
e max.
1 bar
p
e max.
4 bar
-1
-
Screw plug at the inlet
Screw plug at the inlet and outlet
L
V
For air only (without approval)
Medium: aggressive gases (check
suitability), rubber parts coming into
contact with gas made of Viton
(without approval)
Part designations
VGBF..F
VGBF..R
10
1
1
2
3
3
4
4
5
6
6
7
7
8
8
9
9
2
1
Cover cap and adjusting screw
2
Breather screw
Impulse line connection (not on VGBF..05)
4
Outlet
5
Outlet (p
a
) measuring connection
6
Arrow of direction of flow
7
Inlet (p
e
) measuring connection
8
Inlet
9
Type label
10
Damping valve for VGBF 40 – 100..40
Inlet pressure p
e
, outlet pressure p
a
and ambient
temperature: see type label.
Vor dem Öffnen Feder
entspannen!
Release spring
before opening!
Avant d'ouvrir le dôme,
détendre le ressort!
VGBF
CE: 0063AQ0973
Installation
CAUTION
Please observe the following to ensure that the
gas pressure regulator is not damaged during the
installation:
Install the unit free of mechanical stress.
Sealing material, cuttings and other impurities must
not be allowed to get into the regulator housing.
The installation location must be dry. Do not install
the unit in the open air.
Installation in the vertical or horizontal position,
never upside down.
▷
▷
The outlet pressure p
a
is set at the factory with
the spring dome pointing vertically upwards. If
the VGBF is installed with the spring dome in the
horizontal position, check and adjust the outlet
pressure p
a
(see [Changing the outlet pressure
1
Install a filter upstream of the unit, in order to
protect it against impurities in the pipeline.
VGBF..F
>20
mm
4
2
3
5
VGBF..R
>20
mm
4
2
3
6
5