Krom Schroder VGBF 15R Скачать руководство пользователя страница 5

GB-5

D

GB

F

NL

I

E

Technical data

Gas type: natural gas, town gas, LPG (gaseous) 
and biologically produced methane, VGBF..L for air.
Outlet pressure ranges: 

The outlet pressure range is reached through 

the use of different springs (see [Spring table – 
p. 6])
. The regulators are pre-set at the factory to 
20 mbar (red spring).
Rp 1/4 connection for test points or even for a 
pilot gas line: 
at the inlet: VGBF 15 and 25, 
at inlet and outlet: VGBF 40 – 150.

Ambient temperature: -15 to +60°C,
VGBF..V: 0 – 60°C.

Strainers that are possibly fitted serve as flow 
conditioners.
Housing: aluminium,
diaphragms: Perbunan or Viton,
valve seat: aluminium,
valve stem: aluminium,
valve disc: vulcanized Perbunan or Viton seal.
Internal thread: Rp to ISO 7-1,
flanged connection: PN 16 to ISO 7005,
see T12.2.3 brochure for special version,
DN 15 – 50 with NPT thread,
DN 50 – 100 available with ANSI flange.
Impulse line connections: NPT.
Weight [kg]:

Type

Weight

Type

Weight

VGBF 15R

0.9

VGBF 65F

12.0

VGBF 25R

1.9

VGBF 80F

16.1

VGBF 40R

2.9

VGBF 100F

26.0

VGBF 40F

4.8

VGBF 150F

46.5

VGBF 50F

7.7

VGBF..10

Max. inlet pressure p

e max.

: 1 bar.

Feedback via impulse line:
Rp 1/4 connection for DN 15 and 25,
Rp 3/8 connection for DN 40 – 150.
EN 334, Accuracy Class AC 10, Lock up pressure 
class SG 30.

VGBF..40

Max. inlet pressure p

e max.

: 4 bar.

Feedback via impulse line:
Rp 1/4 connection for DN 15 and 25,
Rp 3/8 connection for DN 40 – 150.
EN 334, Accuracy Class AC 10, Lock up pressure 
class SG 30.

VGBF..05

Max. inlet pressure p

e max.

: 500 mbar.

Internal feedback.
EN 88, Class A, Group 2.

Service life

The Pressure Equipment Directive (PED) and the 

Energy Performance of Buildings Directive (EPBD) 
demand regular checks on and maintenance of heat-
ing systems, in order to ensure a high level of use 
in the long term, a clean method of operation and 
safe function.

The service life on which the construction is based, 

hereinafter referred to simply as the “service life”, is 
compiled from the relevant standards. You can find 
further explanations in the applicable rules and regu-
lations and on the afecor website (www.afecor.org).

This information on service life is based on using 

the  product  in  accordance  with  these  operat-
ing instructions. The product must be serviced at 
regular intervals. Once the specified service life has 
been reached, the safety-related functions must be 
checked in accordance with the section entitled 
[Maintenance – p. 4].
If the product passes the aforementioned function 
tests, you can continue to use it until the next sched-
uled maintenance operation. At this point, these tests 
must be repeated.
If the product fails one of the aforementioned tests, 
it must be replaced immediately.

This procedure applies to heating systems. For ther-

moprocessing equipment, observe national regula-
tions.
Service life (based on date of manufacture) in accord-
ance with EN 13611 and EN 88 for VGBF: 15 years.
Long-term use in the upper ambient temperature 
range accelerates the ageing of the elastomer ma-
terials and reduces the service life (please contact 
manufacturer).