Insert new circuit board.

 13 

Follow the reverse procedure when reassembling.

 14 

Re-establish all connections.

 

Wire the new circuit board, see page 3 (4 
Wiring).
 

 

Leave the connection box open for the electrical 
system test.

9.2 electric strength test

 1 

Once the wiring has been carried out and before 

the devices are commissioned, a voltage surge 
test must be carried out.

Test points: mains connection terminals (N, L) with 

respect to PE wire terminal (PE  ).  
Rated voltage > 150 V: 1752 V AC or 2630 V DC,  
testing time 1 second.  
Rated voltage ≤ 150 V: 1488 V AC or 2240 V DC,  
testing time 1 second. 

 2 

Screw the cover onto the connection box once the 
electrical test has been completed successfully.

 3 

The unit is fit for use again.

10 MAIntenAnCe

 CAUtIon

In order to ensure smooth operation, check the 
device function:

 

– Check electrical installations once a year in line 

with local regulations; pay particular attention to 
the PE wire, see page 3 (4 Wiring). 

11 ACCessoRIes

11.1 Pressure switch for gas DG..VC

The pressure switch for gas monitors the inlet pres-

sure p

u

 and the outlet pressure p

d

 

Monitoring the inlet pressure p

u

: the pressure 

switch for gas is mounted on the inlet side.  
Monitoring the outlet pressure p

d

: the pressure 

switch for gas is mounted on the outlet side. 

p

u

p

d

Scope of delivery:  

1 x pressure switch for gas,  

2 x self-tapping retaining screws,  
2 x sealing rings. 

Also available with gold-plated contacts for voltages 

of 5 to 250 V.

 

When retrofitting the pressure switch for gas, see 
enclosed operating instructions “Pressure switch-
es for gas DG..C”, section entitled “Mounting the 
DG..C.. on valVario gas solenoid valves”.

 

The switching point is adjustable via hand wheel.

 1 

 

 2 

 

 3 

type

Adjusting range 

(adjusting 

tolerance = 

± 15% of the 

scale value)

Mean switching 

differential at 

min. and max. 

setting

[mbar]

["WC]

[mbar]

["WC]

DG 17VC

2–17

0.8–6.8 0.7–1.7 0.3–0.8

DG 40VC

5–40

2–16

1–2

0.4–1

DG 110VC 30–110

12–44

3–8

0.8–3.2

DG 300VC

100–

300

40–120

6–15

2.4–8

 

Deviation from the switching point during testing 
pursuant to EN  1854 Gas pressure switches: 

± 15%.

Содержание valVario VAA 1

Страница 1: ...This unit must be installed and commissioned in accordance with the regulations and standards in force These instructions can also be found at www docuthek com 1 2 Explanation of symbols 1 2 3 a b c...

Страница 2: ...ent temperature enclosure inlet pressure and installation position see type label Elster GmbH Osnabr ck Germany Vxx XXXX 3 INSTALLATION CAUTION Incorrect installation Please observe the following to e...

Страница 3: ...ended tightening torques for the connection parts See page 10 12 Technical data f g 4 WIRING WARNING Risk of injury Please observe the following to ensure that no damage occurs Electric shocks can be...

Страница 4: ...on switch can be removed 1 3 2 LV1 N 1 COM 2 Valve open Valve closed 3 1 3 2 LV1 N 1 COM 2 Valve open Valve closed 3 When installing two plugs on VAA a with position switch label the sockets and plugs...

Страница 5: ...adjusted for maximum flow rate Q The markings on the cover cap can be used for coarse adjustment of the flow rate The cover cap can be rotated without changing the current flow rate Allen key 2 5 mm D...

Страница 6: ...ly 2 Close the gas supply 3 4 5 6 7 8 Remove the M20 cable gland or other type of connection VAA without proof of closure switch a b c VAA with proof of closure switch a b c d e VAA with damping unit...

Страница 7: ...nit 1 2 3 4 5 6 7 Open the gas solenoid valve and the gas supply VAA with proof of closure switch Depending on the design of the proof of closure switch one of the two enclosed seals must be inserted...

Страница 8: ...5 13 Switch on the solenoid actuator so that the guide pin becomes visible 14 15 Switch off the solenoid actuator The damping unit is lowered 16 17 M3 18 Open the air supply and switch on the power su...

Страница 9: ...on to the PE wire see page 3 4 Wiring 11 ACCESSORIES 11 1 Pressure switch for gas DG VC The pressure switch for gas monitors the inlet pres sure pu and the outlet pressure pd Monitoring the inlet pres...

Страница 10: ...essure cleaner and or cleaning products 12 2 Mechanical data Gas types clean air The air must be clean and dry in all temperature conditions and must not contain condensate Medium temperature ambient...

Страница 11: ...s been reached safety relevant products must be replaced Designed lifetime based on date of manufacture in accordance with EN 13611 EN 161 for VAA Type Designed lifetime Switching cycles Time years VA...

Страница 12: ...of the Disclosure Table China RoHS2 see certificates at www docuthek com 16 DISPOSAL Devices with electronic components WEEE Directive 2012 19 EU Waste Electrical and Electronic Equipment Directive A...

Отзывы: