Krom Schroder valVario VAA 1 Скачать руководство пользователя страница 3

VAA · Edition 05.22

EN-3

test points on both sides, see accessories. 

p

d

p

u

 

 

The seals in some gas compression fittings 

are approved for temperatures of up to 70°C 
(158°F). This temperature limit will not be ex-
ceeded if the flow through the pipe is at least 

1  m

3

/h (35.31  SCFH) of gas and the maxi-

mum ambient temperature is 50°C (122°F). 

 

 1 

Remove the adhesive label or screw cap from the 

inlet and outlet.

 2 

Obey the direction of flow as marked on the hous-

ing.

3.1 VAA with flanges 

 a 

 

 b 

 

 c 

3.2  VAA without flanges 

 a 

 

 b 

 

 c 

 

O-ring (Fig. 

c

) must be fitted. 

 d 

 

 e 

 

Note the recommended tightening torques for the 
connection parts. See page 10 (12 Technical 
data)
 

 f 

 

 g 

4 WIRInG

 WARnInG

Risk of injury!
Please observe the following to ensure that no 
damage occurs:

 

– Electric shocks can be fatal! Before working on 

possible live components, ensure the unit is 
disconnected from the power supply.

 

– The solenoid actuator heats up during 

operation. Surface temperature approx. 85°C 
(approx. 185°F).

 

Use temperature-resistant cable (> 80°C).

 1 

Disconnect the system from the electrical power 

supply.

 2 

Shut off the air supply.

 

Wiring to EN 60204-1.

 

Push through and remove the knock-out in the 
connection box before removing the cover. If the 
M20 cable gland or plug is already fitted, it is not 
necessary to remove the knock-out.

 3 

 

 4 

M20 cable gland

 a 

 

 b 

 

 c 

 

 d 

 

 e 

(+)

LV1

N

(-)

Содержание valVario VAA 1

Страница 1: ...This unit must be installed and commissioned in accordance with the regulations and standards in force These instructions can also be found at www docuthek com 1 2 Explanation of symbols 1 2 3 a b c...

Страница 2: ...ent temperature enclosure inlet pressure and installation position see type label Elster GmbH Osnabr ck Germany Vxx XXXX 3 INSTALLATION CAUTION Incorrect installation Please observe the following to e...

Страница 3: ...ended tightening torques for the connection parts See page 10 12 Technical data f g 4 WIRING WARNING Risk of injury Please observe the following to ensure that no damage occurs Electric shocks can be...

Страница 4: ...on switch can be removed 1 3 2 LV1 N 1 COM 2 Valve open Valve closed 3 1 3 2 LV1 N 1 COM 2 Valve open Valve closed 3 When installing two plugs on VAA a with position switch label the sockets and plugs...

Страница 5: ...adjusted for maximum flow rate Q The markings on the cover cap can be used for coarse adjustment of the flow rate The cover cap can be rotated without changing the current flow rate Allen key 2 5 mm D...

Страница 6: ...ly 2 Close the gas supply 3 4 5 6 7 8 Remove the M20 cable gland or other type of connection VAA without proof of closure switch a b c VAA with proof of closure switch a b c d e VAA with damping unit...

Страница 7: ...nit 1 2 3 4 5 6 7 Open the gas solenoid valve and the gas supply VAA with proof of closure switch Depending on the design of the proof of closure switch one of the two enclosed seals must be inserted...

Страница 8: ...5 13 Switch on the solenoid actuator so that the guide pin becomes visible 14 15 Switch off the solenoid actuator The damping unit is lowered 16 17 M3 18 Open the air supply and switch on the power su...

Страница 9: ...on to the PE wire see page 3 4 Wiring 11 ACCESSORIES 11 1 Pressure switch for gas DG VC The pressure switch for gas monitors the inlet pres sure pu and the outlet pressure pd Monitoring the inlet pres...

Страница 10: ...essure cleaner and or cleaning products 12 2 Mechanical data Gas types clean air The air must be clean and dry in all temperature conditions and must not contain condensate Medium temperature ambient...

Страница 11: ...s been reached safety relevant products must be replaced Designed lifetime based on date of manufacture in accordance with EN 13611 EN 161 for VAA Type Designed lifetime Switching cycles Time years VA...

Страница 12: ...of the Disclosure Table China RoHS2 see certificates at www docuthek com 16 DISPOSAL Devices with electronic components WEEE Directive 2012 19 EU Waste Electrical and Electronic Equipment Directive A...

Отзывы: