background image

GB-3

D

GB

F

NL

I

E

Wiring

 CAUTION

Please observe the following to ensure that the 
DL..K is not damaged during operation:

–   If the DL..G (DL..TG) has switched a volt-

age > 24 V (> 30 V) and a current > 0.1 A at 
cos φ = 1 or > 0.05 A at cos φ = 0.6 once, 
the gold plating on the contacts will have been 
burnt through. It can then only be operated at 
this power rating or higher power rating.

–   Note the switching capacity, see page  

(Technical data).

 

In the case of high humidity, we recommend 
using a pressure switch with gold contact due to 
its higher resistance to corrosion. Closed-circuit 
current monitoring is recommended under dif-
ficult operating conditions.

 

In the case of low switching capacities, such as 
24 V, 8 mA, for example, we recommend using 
an RC module (22 Ω, 1 μF) in air containing 
silicone or oil.

 1 

  Disconnect the system from the electrical power 

supply.

M16 x 1,5: 

 4,5 – 10 mm

COM

3

NC

1

NO

2

NO

2

NC

1

COM

3

L1(+)

5

4

3

2

Adjustment

 

The switching pressure can be adjusted using the 

hand wheel and scale. The switching pressure 
differs from the adjusted setpoint by a maximum 
of ± 15%, when it has been set for increasing 
pressure and with a vertical diaphragm.

Type

Adjusting 

range 

[Pa]

Mean 

switching 

differential 

at min. and 

max. setting 

[Pa]

Deviation from 

the switching 

point during 

testing 

pursuant to 

EN 1854 or 

by agreement

min. max. min. max.

DL 3,3K 20

330

8

20

± 7  Pa/± 15%

DL 3,5K 30

350

10

20

± 5  Pa/± 15%

DL 4,5K 30

500

12

25 ± 5  Pa/± 15%

DL 5,1K 100

510

15

30

± 15%

DL 8K

50

800

17

30

± 14 

Pa/± 15%

DL 11K 100 1100

20

35

± 20 

Pa/± 15%

DL 16K 400  1600

30

40

± 15%

DL 24K 200 2400 45

55

± 40 

Pa/± 15%

DL 40K 500 4000 70

90

± 15%

Type

Adjusting 

range 

["WC]

Mean 

switching 

differential 

at min. 

and max. 

setting 

["WC]

Deviation from 

the switching 

point during 

testing pursuant 

to EN 1854 or 

by agreement

min. max. min. max.

DL 3,5KT 0.12 1.4 0.04 0.08

± 0.02 

"WC/± 15%

DL 4,5KT 0.12

2

0.05 0.10

± 0.02 

"WC/± 15%

DL 8KT

0.20 3.2 0.07 0.12

± 0.06 

"WC/± 15%

DL 11KT 0.4 4.4 0.08 0.14

± 0.08 

"WC/± 15%

DL 16KT 1.6

6.4 0.12 0.16

± 15%

DL 24KT 0.8 9.6 0.18 0.22

± 0.16 

"WC/± 15%

DL 40KT 2.0 16.0 0.28 0.36

± 15%

 1 

  Disconnect the system from the electrical power 

supply.

+

+

1

NC

2

NO

3

COM

5

4

3

2

NO

2

NC

1

COM

3

Содержание DL K Series

Страница 1: ... limb CAUTION Indicates possible material damage All interventions may only be carried out by qualified gas technicians Electrical interventions may only be carried out by qualified electricians Conversion spare parts All technical changes are prohibited Only use OEM spare parts Transport On receipt of the product check that the delivery is complete see Part designations Report any trans port dama...

Страница 2: ...erwise there is a risk of icing of condensation at subzero temperatures the switching point shifting or corrosion in the device which can lead to malfunctions In the case of uneven ground secure the pres sure switch to the mounting plate or air duct with only two screws on the same side in order to avoid subjecting the pressure switch to me chanical stress Protect the connections against dirt or m...

Страница 3: ... using the hand wheel and scale The switching pressure differs from the adjusted setpoint by a maximum of 15 when it has been set for increasing pressure and with a vertical diaphragm Type Adjusting range Pa Mean switching differential at min and max setting Pa Deviation from the switching point during testing pursuant to EN 1854 or by agreement min max min max DL 3 3K 20 330 8 20 7 Pa 15 DL 3 5K ...

Страница 4: ...V min 0 01 A to 48 V DC max 1 A DL KT 30 240 V AC 50 60 Hz 5 A resistive or 0 5 A inductive cos ϕ 0 6 DL KTG 30 V AC DC 0 1 A resistive or 0 05 A inductive cos ϕ 0 6 Ambient temperatures DL K 15 to 85 C 5 to 185 F DL KT 40 to 60 C 40 to 140 F Line entrance M16 1 5 cable diameter 4 5 to 10 mm Enclosure to IEC 60529 IP 54 Diaphragm tempered LSR diaphragm system Max inlet pressure pu or differential ...

Отзывы: