Krom Schroder DL H Series Скачать руководство пользователя страница 4

DL..H, DL..N · Edition 05.22

EN-4

4 WIRInG

Pressure switch DL..H, DL..N can be used in 

Zone 1 (21) and 2 (22) hazardous areas if an isolating 

amplifier is installed upstream in the safe area as “Ex-
i” apparatus pursuant to EN 60079-11 (VDE 0170-

7):2012. 

DL..H, DL..N as “simple electrical apparatus” pursuant 
to EN 60079-11:2012 corresponds to the Temperature 
class T6, Group II. The internal inductance/capacitance 
is Li = 0.2 μH/Ci = 8 pF. 

 

If the pressure switch has switched a voltage > 24 V 
(> 30 V) and a current > 0.1 A at cos φ = 1 or 

> 0.05 A at cos φ = 0.6 once, the gold plating 

on the contacts will have been burnt through. It 
can then only be operated at this power rating or 
higher power rating. 

 CAUtIon

 

– To ensure that the DL..H, DL..N is not damaged 

during operation, note the switching capacity, 
see page 6 (8 Technical data). 

In the case of low switching capacities, such as 24 V, 
8 mA, for example, we recommend using an RC mod-
ule (22 Ω, 1 μF) in air containing silicone or oil.

NO

C = 1 µF

R = 22 Ω

2

NC

1

COM

3

 1 

Disconnect the system from the electrical power 

supply.

 2 

 

 3 

 

 4 

 

 5 

M16 x 1,5:

ø 4–10 mm

 6 

Wire as shown on the connection diagram.

 7 

Tighten the M16 gland) (1/2" NPT conduit).

 

Contacts 3 and 2 close when subject to increasing 

pressure. Contacts 1 and 3 close when subject 
to falling pressure. With the NO contact, the NC 
contact is omitted.

COM

3

NC

1

NO

2

NO

2

NC

1

COM

3

L1

5 ADJUstMent

 

The switching point is adjustable via hand wheel.

 1 

Disconnect the system from the electrical power 

supply.

 2 

Unscrew the housing cover.

 

Once the settings have been adjusted successfully, 
fit the housing cover again. Note the tightening 
torques, see page 6 (8 Technical data). 

 3 

Connect an ohmmeter.

COM

3

NC

1

NO

2

NO

2

NC

1

COM

3

 4 

Set the switching point using the hand wheel.

 5 

Connect a pressure gauge.

 6 

0

1 cm = 1 mbar

(0.4" = 0.4"WC)

 7 

Apply pressure. In doing so, monitor the switching 

point on the ohmmeter and the pressure gauge.

 8 

If the DL..H, DL..N does not trip at the desired 

switching point, correct the adjusting range using 
the hand wheel. Relieve the pressure and repeat 
the process. 

5.1 Adjusting range

type

Adjust-

ing 

range

1)

 

[mbar]

Max. 

inlet 

pres-

sure

2)

 

[mbar]

Reset 

pres-

sure

3)

 

[mbar]

DL 10..H, 

DL 10..N

1–10

300

0.4–1

DL 50..H, 

DL 50..N

2.5–50

300

1–2

DL 150..H, 

DL 150..N

30–150

300

2–5

type

Adjust-

ing 

range

1)

 

["WC]

Max. 

inlet 

pres-

sure

2)

 

["WC]

Reset 

pres-

sure

3)

 

["WC]

DL 10..H, 

DL 10..N

0.4–4

117

0.16–

0.4

DL 50..H, 

DL 50..N

1–20

117

0.4–0.8

DL 150..H, 

DL 150..N

12–60

117

0.8–2

1) Adjusting tolerance = ± 15% of the scale value.

2) Max. inlet pressure = withstand pressure.
3) Difference between switching pressure and possible 

reset.

Deviation from the switching point during testing pur-
suant to EN 1854 Air pressure switches: ± 15%.

Содержание DL H Series

Страница 1: ...ed in accordance with the regulations and standards in force These instructions can also be found at www docuthek com 1 2 Explanation of symbols 1 2 3 a b c Action Instruction 1 3 Liability We will not be held liable for damage resulting from non observance of the instructions and non com pliant use 1 4 Safety instructions Information that is relevant for safety is indicated in the instructions as...

Страница 2: ...2 6 3 4 5 1 Upper housing section with cover 2 Lower housing section 3 Hand wheel 4 M16 cable gland 5 Manual reset 6 Test key DL A 2 3 Type label DL CE 2 1 3 D 49018 Osnabrück Germany Max inlet pressure withstand pressure mains volt age ambient temperature enclosure see type label 3 INSTALLATION CAUTION Please observe the following to ensure that the unit is not damaged during installation Droppin...

Страница 3: ...9 5 0 4 15 5 0 6 45 1 8 54 5 2 1 6 0 2 ø 3 x 16 ø 0 11 x 0 6 64 2 5 DL AH DL AN DL KH DL KN 28 5 1 1 M16 x 1 5 NPT Conduit 28 5 1 1 M16 x 1 5 NPT Conduit 3 3 Connecting the pressure line DL A upon delivery port 2 is closed off by a rub ber cap DL A 1 Rp 1 4 1 4 NPT 2 ø 4 75 x 1 mm 3 ø 4 75 x 1 mm 4 Rp 1 8 1 8 NPT 1 2 3 4 Te st Positive pressure port 1 or 2 Negative pressure port 3 after unscrewing...

Страница 4: ...close when subject to falling pressure With the NO contact the NC contact is omitted COM 3 NC 1 NO 2 NO 2 NC 1 COM 3 L1 5 ADJUSTMENT The switching point is adjustable via hand wheel 1 Disconnect the system from the electrical power supply 2 Unscrew the housing cover Once the settings have been adjusted successfully fit the housing cover again Note the tightening torques see page 6 8 Technical data...

Страница 5: ...a restrictor orifice contains non ferrous metals Hole diameter 0 2 mm Order No 75456321 Hole diameter 0 3 mm Order No 75441317 7 2 Z angle bracket 11 3 0 44 7 0 27 7 5 0 3 40 1 6 59 2 3 ø 5 5 0 22 ø 6 0 22 ø 4 2 0 17 10 0 39 1 0 04 For DL K Order No 74916158 For DL A Order No 74913661 7 3 Fastening set with screws U shape bracket M4 x 10 M4 x 12 50 1 97 47 5 1 87 75 2 95 30 1 18 20 0 79 25 0 98 45...

Страница 6: ...8 TECHNICAL DATA 8 1 Ambient conditions Enclosure to IEC 60529 IP 54 IP 65 Permitted ambient temperature in operation 15 to 60 C 5 to 140 F Storage and transport temperatures 20 to 40 C 4 to 104 F Micro switch to EN 61058 1 Gas types air or flue gas no flammable gases no aggressive gases Icing condensation and dew in and on the unit are not permitted Safety class II to VDE 0106 1 This unit is not ...

Страница 7: ...ucts must be replaced Designed lifetime based on date of manufacture in accordance with EN 13611 EN 1854 for DL H DL N 10 Jahre years You can find further explanations in the applicable rules and regulations and on the afecor website www afecor org This procedure applies to heating systems For ther moprocessing equipment observe local regulations 10 CERTIFICATION Declaration of conformity We the m...

Страница 8: ...At the end of the product life number of op erating cycles reached dispose of the pack aging and product in a corresponding recycling centre Do not dispose of the unit with the usu al domestic refuse Do not burn the product On request old units may be returned carriage paid to the manufacturer in accordance with the relevant waste legislation requirements 2022 Elster GmbH We reserve the right to m...