BCU 560, BCU 565 · Edition 02.16
53
11 Parameters
Any changes to parameters will be saved to the parameter chip card.
Name
Parameter Value range Description
Factory default
settings
Burner 1 FS1 flame signal switch-off
01
0 – 20
Burner 1 FS1 flame signal switch-off thresh-
old in µA
2
(5 when P04 = 1)
04
0
1
2
Ionization electrode
UVS sensor
UVD sensor
0
06
0
2
3
5
Off
Intermittent operation with UVS
Continuous operation with ionization/UVD
menox intermittent
0
07
1
2
3
1 start-up attempt
2 start-up attempts
3 start-up attempts
1
09
0
1
4
Off
Burner 1
Max. 5 × for burner 1 in 15 min.
0
15
0
1
2
Off
With safety shut-down
With fault lock-out
2
16
0
1
Off
On
19
0; 1; 2
Time in seconds
1
menox pre-ventilation time tVLM
28
0 – 250
Time in seconds
0
34
0 – 6000
Time in seconds
6000
Air flow monitoring during pre-
35
0
1
2
Off
With safety shut-down
With fault lock-out
2
36
0 – 250
Time in seconds
0
▼