l
F
ull signal
C
heck if all three switching conditions occur in the correct
sequence and the stated duration
.
I
f not
,
there is a fault in the
measuring system
(
see chapter
"
F
ault recti
fi
cation
"
).
N
ote
:
K
eep in mind that the connected instruments are activated
during the function test
.
B
y doing this
,
you can check the
correct function of the measuring system
.
T
est procedure
A
-
mode
B
-
mode
1
S
imulation of a fault signal
(
approx
.
3
s
)
L
evel relay deenergised
R
elay control
lamp o
ff
R
elay control
lamp o
ff
1
S
imulation of a fault signal
F
ailure lamp
F
ailure lamp
lights
F
ailure lamp
lights
2
S
imulation an empty signal
(
approx
.
1
.
5
s
)
L
evel relay energised
R
elay control
lamp lights
R
elay control
lamp o
ff
2
S
imulation of an empty signal
F
ailure lamp
F
ailure lamp o
ff
F
ailure lamp o
ff
3
S
imulation of a full signal
(
approx
.
1
.
5
s
)
L
evel relay deenergised
R
elay control
lamp o
ff
R
elay control
lamp lights
3
S
imulation of a full signal
F
ailure lamp
F
ailure lamp o
ff
F
ailure lamp o
ff
4
R
eturn to the current operating condition
(
covered
/
uncovered
)
SU
501
E
x
-
S
ignal conditioning instrument
19
S
et up
27953
-
EN
-
050616