![KROHNE OPTIWAVE 400 Series Скачать руководство пользователя страница 22](http://html1.mh-extra.com/html/krohne/optiwave-400-series/optiwave-400-series_supplementary-instructions-manual_2004325022.webp)
3
ELECTRICAL CONNECTIONS
22
OPTIWAVE X400
www.krohne.com
06/2021 - 4006413503 - AD NEPSI OPTIWAVE x400 R03 en
3.6 Ex d ia / Ex iaD tD equipment
3.6.1 General notes
Ex d ia- and Ex iaD tD-approved equipment have two separate compartments. The electronics in
the electronics block compartment are Ex ia-approved and the terminal compartment is Ex d /
Ex tD-approved.
3.6.2 How to connect the electrical cables
Cable glands are supplied on customer demand. If you supply the cable glands, this part must
have a degree of ingress protection IP
≥
6X (IEC 60529). We recommend that you use a part that
has a degree of ingress protection IP
≥
68. Make sure that the cable gland is sealed.
Terminal compartment
•
If you connect electrical wires to the terminals in the flameproof terminal compartment, use
approved flameproof cable glands (M20×1.5 or
½
NPT). The cable glands must have a
certificate that agrees with GB 3836.1 and GB 3836.2. Obey the instructions given on the
certificate. Make sure that the tightening capacity of the cable gland is applicable to the
diameter of the electrical wire.
•
If you use conduits to connect electrical wires to the terminals in the flameproof terminal
compartment, obey the instructions that follow. Make sure that the conduits are correctly
attached and the flameproof compartment is sealed. The conduits must have a certificate
that agrees with GB 3836.1 and GB 3836.2. Use conduit stopping boxes that agree with
precautions given in the certificate and data in standards related to the installation of the
conduit.
Figure 3-4: Compartments in Ex d ia- and Ex iaD tD-approved equipment
1
Electronics block (Ex ia) compartment
2
Terminal (Ex d / Ex tD) compartment
DANGER!
If you must open the electronics block compartment to remove the electronics blocks for
servicing, de-energize the device. It is not necessary to disconnect the wires from the Ex d /
Ex tD terminals.
If you must remove the terminal block for servicing, do not open the terminal compartment in a
potentially explosive atmosphere.
WARNING!
Use only Ex d-approved cable glands and adaptors for Ex d applications. Use only Ex tD-
approved cable glands and adaptors for Ex tD applications.