background image

4

 ELECTRICAL CONNECTIONS 

16 

OPTITEMP TT 53 C/R

www.krohne.com

06/2018 - 4006523501 - MA OPTITEMP TT 53 R01 en

4.1  Safety instructions

DANGER!

All work on the electrical connections may only be carried out with the power disconnected. Take 
note of the voltage data on the nameplate!

DANGER!

Observe the national regulations for electrical installations!

DANGER!

The transmitter is protected against polarity reversal. No damage will occur to the device if the 
polarity of the supply voltage is switched. The output will then indicate 0 mA.

DANGER!

In potentially explosive areas, the intrinsically safe versions must be used.
The TT 53 C Ex / TT 53 R Ex (intrinsically safe) can be installed in potentially hazardous area zone 
0, 1 and 2.
The TT 53 C Ex / TT 53 R Ex (intrinsically safe) can be installed in potentially hazardous area zone 
1 and 2 and the input may be connected to temperature sensors installed in zone 0.
The intrinsically safe versions must be supplied by an intrinsically safe power supply unit or 
Zener barrier placed outside of the potentially explosive area.

DANGER!

The transmitter may be operated in areas with potentially explosive atmospheres if the voltage 
supply is ensured by means of an associated apparatus.
The safety instructions for operation in potentially explosive areas must be observed.
In potentially explosive areas only Ex approved HART

®

 modems must be used.

In order to ensure reliable HART

®

 communication with this transmitter, the maximum cable 

length of the output circuit must be observed. For detailed information refer to Cable length on 
page 22.

WARNING!

Observe without fail the local occupational health and safety regulations. Any work done on the 
electrical components of the measuring device may only be carried out by properly trained 
specialists.

INFORMATION!

Look at the device nameplate to ensure that the device is delivered according to your order. 
Check for the correct supply voltage printed on the nameplate(Applies only to the intrinsically 
safe versions.)

DANGER!

For the transmitters used in hazardous areas following special conditions have to be considered:
The communication interface (USB connection) may only be connected to the associated TT-CON 
interface if the temperature transmitter is outside of the hazardous area. If certified TT-CON Ex 
interface is used, a connected sensor may be located in the hazardous area. If non-Ex TT-CON 
interface is used, a connected sensor shall not be located in the hazardous area. 
For the permitted ambient temperature range, refer to Temperature data for areas with 
potentially explosive atmospheres on page 47
The transmitter shall be mounted into a suitable enclosure that provides a degree of protection 
of at least IP20.

Содержание OPTITEMP TT 53 C

Страница 1: ...TITEMP TT 53 C R OPTITEMP TT 53 C R OPTITEMP TT 53 C R OPTITEMP TT 53 C R Handbook Handbook Handbook Handbook KROHNE 06 2018 4006523501 MA OPTITEMP TT 53 R01 en The documentation is only complete when...

Страница 2: ...any part thereof without the prior written authorisation of KROHNE Messtechnik GmbH Subject to change without notice 2 O www krohne com 06 2018 4006523501 MA OPTITEMP TT 53 R01 en Copyright 2018 by KR...

Страница 3: ...mitter 13 3 2 Rail mounting kit for in head transmitters 14 3 3 Rail mount transmitter 15 4 Electrical connections 16 4 1 Safety instructions 16 4 2 Electrical connections of in head transmitter 17 4...

Страница 4: ...s availability 37 6 3 Availability of services 37 6 4 Returning the device to the manufacturer 37 6 4 1 General information 37 6 4 2 Form for copying to accompany a returned device 38 6 5 Disposal 38...

Страница 5: ...ters might cause an explosion that can result in fatal injuries DANGER Responsibility for the correct use of the devices with special regard to suitability intended use and the field of application li...

Страница 6: ...ctive 93 68 EC RoHS Directive 2011 65 EU harmonized standard EN 50581 2012 Radio Equipment Directive RED 2014 53 EU The manufacturer certifies successful testing of the product by applying the CE mark...

Страница 7: ...n over the Internet e g when communicating by e mail may involve gaps in security It is not possible to protect such data completely against access by third parties We hereby expressly prohibit the us...

Страница 8: ...ion To prevent any injury to the user or damage to the device it is essential that you read the information in this document and observe applicable national standards safety requirements and accident...

Страница 9: ...warnings must be observed without fail Even partial disregard of this warning can lead to serious health problems and even death There is also the risk of seriously damaging the device or parts of th...

Страница 10: ...ilable for downloading on our website You can find configuration instructions in the ConSoft reference manual ConSoft is compatible with Windows XP Vista 7 8 8 1 10 TT 53 C In head transmitter The in...

Страница 11: ...or round nameplate 1 Product name 2 CE marking EC conformity 3 Ex relevant electrical data 4 Part number serial number yyww year and week of manufacturing and batch number 5 Printable field sensor con...

Страница 12: ...e marking 4006067302 Nyyww xxxxxx PO ZZZZZZZZZ www krohne com OPTITEMP TT 53 R KIWA 17ATEX0056 X IECEx KIWA 17 0030X 0539 II 1 G Ex ia IIC T6 T4 Ga Max ambient 85 C Uo 6 5 V Io 11 7 mA Po 19 1 mW Co 2...

Страница 13: ...lly safe version must be supplied by an intrinsically safe power supply unit or Zener barrier placed outside of the potentially explosive zone The Ex transmitter must be installed in a housing with th...

Страница 14: ...he transmitter until it is attached to the clip INFORMATION The rail mounting kit allows to install the in head transmitter on a rail according to EN 60715 DIN 50022 The kit does not belong to the sta...

Страница 15: ...22 1 Fix the upper part of the transmitter onto the rail 2 Press the lower part of the transmitter against the rail 3 To remove the transmitter bend the locking device using a small screwdriver Carefu...

Страница 16: ...ation in potentially explosive areas must be observed In potentially explosive areas only Ex approved HART modems must be used In order to ensure reliable HART communication with this transmitter the...

Страница 17: ...wire connection Pt100 Pt100 Pt100 Pt100 Pt1000 Ni100 Ni120 Cu10 Pt1000 Ni100 Ni120 Cu10 Pt1000 Ni100 Ni120 Cu10 Pt1000 Ni100 Ni120 Cu10 3 wire connection 3 wire connection 3 wire connection 3 wire con...

Страница 18: ...ure 4 1 Connection diagram 1 Voltage supply 8 5 36 VDC terminals 6 7 2 HART Modem 3 Input 4 Output 5 Thermocouple 6 Pt100 3 wire connection INFORMATION The HART modem is connected parallel to the outp...

Страница 19: ...N The HART modem is connected parallel to the output load or parallel to the output of the transmitter DANGER The transmitter may be operated in areas with potentially explosive atmospheres if the vol...

Страница 20: ...00 Pt1000 Ni100 Ni120 Cu10 Pt1000 Ni100 Ni120 Cu10 Pt1000 Ni100 Ni120 Cu10 Pt1000 Ni100 Ni120 Cu10 3 wire connection 3 wire connection 3 wire connection 3 wire connection Pt100 Pt100 Pt100 Pt100 Pt100...

Страница 21: ...tage supply 8 5 36 VDC and output 4 20 mA INFORMATION The HART modem is connected parallel to the output load or parallel to the output of the transmitter The load must be at least 250 for HART to wor...

Страница 22: ...ice For multiple connections Multidrop mode the following formula shall be used L 65 x 106 R x C x Cn x 5000 10000 C with L cable length m or ft R load resistance incl the resistance of any Zener barr...

Страница 23: ...oes not need any power or other external connection just to be close to the smartphone The APP makes it possible to read write save and share settings directly in the field The logging function give t...

Страница 24: ...e INFORMATION In order to ensure reliable HART communication with this transmitter the loop resistance must be at least 250 If the USB interface configuration modem is connected to the transmitter the...

Страница 25: ...transmitter or other HART devices The current outputs of the devices must be passive 1 Primary master 2 HART modem 3 HART signal 4 Other HART devices or this transmitter refer also to 7 5 Terminal 7 6...

Страница 26: ...pecifications DANGER Only an Ex approved HART modem located in safe area may be connected to a transmitter placed in potentially explosive area Menu Parameter Factory settings Device Root menu Sensor...

Страница 27: ...on below 1 2 00 Replace the USB interface with newer version 3 Is a ConSoft version 1 2 0 0 or higher installed on your PC 3a No 3b Yes 4 Download the current ConSoft version from our website and inst...

Страница 28: ...face TT CON Ex to the transmitter Figure 5 1 Connection during configuration of in head transmitter a PC configuration kit b PC software ConSoft 1 Input intrinsically safe 2 RLoad intrinsically safe 3...

Страница 29: ...safe 4 Communication with USB interface and a PC software ConSoft 5 Connection to USB interface and a PC software ConSoft is not permitted if Ex version of TT 53 R TT 53 R Ex is placed in the classifi...

Страница 30: ...an be configured via the PC software as AMS Asset Management System and Simatic PDM Asset Management Solutions Device Manager AMS Asset Management Solutions Device Manager AMS Asset Management Solutio...

Страница 31: ...ffline Root Menu for offline configuration 5 9 Configuration with PACTware PACTware is a DTM FDT enabled PC software which can be downloaded from krohne com To be able to configure the transmitters vi...

Страница 32: ...l revisions the Field Device Status had to be set to 0 if a communication error is reported Messages in AMS PDM and FC 475 device diagnostic Actions Standard NE 107 Signal 12 Error message Error corre...

Страница 33: ...c diagnostic for more information about sensors and transmitter Transmitter M Device variable alert Check device specific diagnostic for more information about sensors and transmitter Transmitter F Cr...

Страница 34: ...valid Check Linearization table settings If error remains replace device Transmitter F Loop voltage too low N A Transmitter F Dac out of range Digital to Analog Converter out of max range Power cycle...

Страница 35: ...ter M Linearization table Overrange N A Transmitter S High Alarm Check the sensor and sensor connection If error remains replace the sensor Transmitter S Low Alarm Check the sensor and sensor connecti...

Страница 36: ...ion software 5 14 System or sensor error correction System error correction System error correction System error correction System error correction To perform a System error correction a dry block cel...

Страница 37: ...d installation kit 70ADA00017 Ex Configuration kit including Ex approved modem Not a HART modem software Consoft and cables for USB connection 4001107902 HART PC modem USB 70MEM00003 TT CON BT interfa...

Страница 38: ...e when it is returned Date Signature Stamp LEGAL NOTICE Disposal must be carried out in accordance with legislation applicable in your country Separate collection of WEEE Waste Electrical and Electron...

Страница 39: ...tance of metals increases according to a mathematical function as the temperature rises This effect is taken advantage of by resistance temperature sensors to measure temperature The Pt100 temperature...

Страница 40: ...red If however the measuring point and the cold junction are at the same temperature no thermoelectric voltage is generated The degree of thermoelectric voltage also known as electromotive force EMF d...

Страница 41: ...s Features HART compliance The transmitters are fully compliant with the HART 7 protocol HART 7 offers the possibility to receive diagnostic information such as sensor errors or sensor conditions tran...

Страница 42: ...tegory In head transmitter Housing IP65 Terminals IP00 Rail mount transmitter Housing IP20 Terminals IP20 Installation conditions Mounting In head transmitter DIN B head or larger DIN rail with adapte...

Страница 43: ...es Input thermocouples Input thermocouples Input thermocouples T C type B Pt30Rh Pt6Rh IEC 60584 400 1800 C 752 3272 F T C type C W5Re W26Re ASTM E 988 0 2315 C 32 4199 F T C type D W3Re W25Re ASTM E...

Страница 44: ...ser friendly tool for wireless configuration through Bluetooth or NFC technology Communication via Bluetooth requires the Bluetooth interface TT CON BT which can be ordered from the manufacturer Alter...

Страница 45: ...fe TT 53 C Ex intrinsically safe TT 53 C Ex intrinsically safe ATEX KIWA 17ATEX0054 X II 1G Ex ia IIC T6 T4 Ga IECEx IECEx KIWA 17 0028X Ex ia IIC T6 T4 Ga TT 53 R Ex intrinsically safe TT 53 R Ex int...

Страница 46: ...ions In head transmitter In head transmitter In head transmitter In head transmitter Rail mount transmitter Rail mount transmitter Rail mount transmitter Rail mount transmitter Dimensions mm inch a 33...

Страница 47: ...ead transmitter Intrinsically safe transmitter Rail mount transmitter Rail mount transmitter Rail mount transmitter Rail mount transmitter Intrinsically safe transmitter Temperature class Ambient temp...

Страница 48: ...maximum permissible output load permissible RLoad U 8 5 0 022 INFORMATION Shaded areas shows the working area of the HART communication Standard transmitter Figure 7 3 Output load diagram X Power sup...

Страница 49: ...mount transmitter Rail mount transmitter Rail mount transmitter Rail mount transmitter Intrinsically safe transmitter TT 53 R Ex Output terminals 6 7 Input terminals 1 2 3 4 Ui Vmax 30 VDC Uo U0C 6 5...

Страница 50: ...01 of span per C RTD Cu10 50 260 83 1 5 C or 0 2 of span 0 02 of span per C T C type B 400 1800 700 1 0 C or 0 2 of span 2 0 01 of span per C T C type C 0 2315 200 1 0 C or 0 2 of span 2 0 01 of span...

Страница 51: ...F or 0 1 of span 2 0 006 of span per F T C type C 32 4199 360 1 8 F or 0 1 of span 2 0 006 of span per F T C type D 32 4199 360 1 8 F or 0 1 of span 2 0 006 of span per F T C type E 454 1832 90 0 9 F...

Страница 52: ...degree of protection of at least IP20 North America 1 The configuration of the associated apparatus or intrincically safe equipment or simple apparatus shall be approved 2 Safety barriers must be ins...

Страница 53: ...06 01 4 If the cable parameters are unknown the following values shall be used Capacitance 200 pF m 60pF feet Inductance 0 66 H m 0 20 H feet 5 If the safety barrier requires an earth conection then t...

Страница 54: ...9 NOTES 54 OPTITEMP TT 53 C R www krohne com 06 2018 4006523501 MA OPTITEMP TT 53 R01 en...

Страница 55: ...NOTES 9 55 OPTITEMP TT 53 C R www krohne com 06 2018 4006523501 MA OPTITEMP TT 53 R01 en...

Страница 56: ...cess Analysis Services Head Office KROHNE Messtechnik GmbH Ludwig Krohne Str 5 47058 Duisburg Germany Tel 49 203 301 0 Fax 49 203 301 10389 info krohne com KROHNE 06 2018 4006523501 MA OPTITEMP TT 53...

Отзывы: