 SPECIAL CONDITIONS 

20 

OPTIBAR 5060

www.krohne.com

04/2021 - 4005260702 - AD OPTIBAR 5060 Exta R02 en

4.1  Grounding

The OPTIBAR * 5060 VGK5/6/D*A/W/V R/H/1/7/S/T*******(*)************** must be grounded.

In the case of the version with remote housing of the OPTIBAR * 5060 VGK5/6/D*A/W/V 

R/H/1/7/S/T*******(*)************** pressure transmitters, the equipotential bonding must be 

provided in the complete mounting area of the connection cable between electronics housing 

and transmitter housing.

4.2  Cable entry

The supplied cable entry is suitable for the housing temperature range certified for the

OPTIBAR * 5060 VGK5/6/D*A/W/V R/H/1/7/S/T*******(*)**************-.

Cable entries may only be replaced by the same type or suitable cable glands separately certified 

as per ATEX/IECEx with minimum IP 66 must be used.

If a cable entry other than the one provided is used, the separately certified cable entry 

determines the maximum permitted ambient temperature at the electronics housing (maximum 

values: -40°C / -40°F, +80°C / +176°F).

4.3  Material resistance

The OPTIBAR * 5060 VGK5/6/D*A/W/V R/H/1/7/S/T*******(*)************** should only be used 

in media against which the wetted materials are sufficiently resistant.

4.4  Housing cover lock

In the case of the single chamber housing versions the housing cover must be turned until it 

stops before starting up and using the OPTIBAR * 5060 VGK5/6/D*A/W/V 

R/H/1/7/S/T*******(*)************** in explosive atmospheres. It should be secured using the 

lock on the cover.

For the double chamber housing versions the housing cover on the terminal compartment and 

the housing cover on the electronics compartment must be turned until they stop before starting 

up and using the OPTIBAR * 5060 VGK5/6/D*A/W/V R/H/1/7/S/T*******(*)************** in 

explosive atmospheres. They should be secured using the appropriate lock on the cover.

Содержание OPTIBAR 5060

Страница 1: ...a IIIC TX C Da Da Db Da Dc Db II 1 2 D 1 2D Ex ia ia ia tb ia IIIC TX C Da Db Da Db IECEX Ex ta ia ia tb ia tc tb ia IIIC TX C Da Da Db Da Dc Db Ex ia ia ia tb ia IIIC TX C Da Db Da Db OPTIBAR 5060 Su...

Страница 2: ...s 9 2 6 Thermal parameters 10 2 6 1 Ingress protection according to 60529 12 2 7 Electrical data 12 2 7 1 OPTIBAR 5060 VGK5 6 D A W V R H 7 S T 12 2 7 2 OPTIBAR 5060 VGK5 6 D A W V R S 1 13 2 7 3 OPTI...

Страница 3: ...tal or plastic housing remote version with electronics housing in Ex free area The OPTIBAR 5060 VGK5 6 D A W V R H 1 7 S T are suitable for use in explosive atmospheres with flammable dust for applica...

Страница 4: ...is The X after the certificate number refers to special conditions for safe use of the device which have been listed in these instructions If needed the IEC certificate can be downloaded from the man...

Страница 5: ...PTIBAR 5060 1 Observe the instructions 2 Marking of notified body and CE marking 3 Hardware version 4 Product name and type code 5 Permissible temperature range 6 Nominal range Permissible process pre...

Страница 6: ...are version 3 Product name and type code 4 Permissible temperature range 5 Nominal range Permissible process pressure 6 Electronics power supply and signal output 7 Ingress protection and material of...

Страница 7: ...us areas requiring equipment category 2D The process connection element is installed in the separating wall which separates areas in which equipment category 2D or 1D are required The sensor with the...

Страница 8: ...X C Da Da Db Da Dc Db Ex ta ia ia tb ia tc tb ia IIIC TX C Da Da Db Da Dc Db II 1G 1 2G 2G Ex ia IIC T6 T1 Ga Ga Gb Gb Ex ia IIC T6 T1 Ga Ga Gb Gb T see thermal parameters OPTIBAR 5060 VGK5 6 D A W V7...

Страница 9: ...electronics and sensor housing are designed as protection type Ex tb protection by enclosure for use in Zone 21 the pressure sensor is designed in Ex ia Ex tb ia The electronics and sensor housing ar...

Страница 10: ...equipment Range Permissible temperature range Electronics housing 40 60 C 40 140 F Probe 40 60 C 40 140 F Max surface temperature Electronics housing Z H A S T P F Ambient temperature 42 K Table 2 2 A...

Страница 11: ...ng Z H A S T P F Ambient temperature 20 K Probe Process temperature 41 K Table 2 6 Application for category 1 2D 1 3D equipment with temperature adapter Probe 40 150 C 40 302 F Range Permissible tempe...

Страница 12: ...housing 40 60 C 40 140 F Max surface temperature Probe Process temperature 41 K Table 2 9 Application for category 1 2 D equipment Protection class Ingress protection At probe category 1D or 2D IP68 A...

Страница 13: ...signal circuit I Terminals 5 6 7 8 For connection to the circuit terminals 5 6 7 8 of an OPTIBAR 5060 with integrated electronics S or T as differential pressure measurement Table 2 14 Electrical dat...

Страница 14: ...Z H A S T P F U Probe circuit Terminals 1 yellow 2 white 3 red 4 black In the version with a line between the electronics housing and the transmitter housing the supplied wire may have a maximum leng...

Страница 15: ...he information given in the manuals and the supplementary instructions must be observed at all times Install pressure transmitters so that the device is not in a pneumatic flow there is no danger from...

Страница 16: ...20 2 Ex ta 3 Ex ia Figure 3 2 Sensor is completely mounted in zone 21 1 Zone 21 2 Ex tb 3 Ex ia Observe the thermal data for equipment category 2D The hazardous area technical requirements for zone 21...

Страница 17: ...nd the filter element only stainless steel and aluminium housing with cable entries certified for use in dust Ex environments and no plug connectors are permitted Figure 3 4 The sensor is installed in...

Страница 18: ...plastic housing electro polished stainless steel housing and plug con nectors are permitted for the electronics and terminal housing cable entries and the filter element Figure 3 6 Electronics and co...

Страница 19: ...1 1 Zone 21 2 Ex tb ia 3 Ex ia 4 Zone 20 The connecting line is an intrinsically safe signal circuit The hazardous area technical requirements for zone 21 apply to the electronics and terminal housing...

Страница 20: ...other than the one provided is used the separately certified cable entry determines the maximum permitted ambient temperature at the electronics housing maximum values 40 C 40 F 80 C 176 F 4 3 Materi...

Страница 21: ...com 04 2021 4005260702 AD OPTIBAR 5060 Exta R02 en Figure 4 1 Single chamber housing 1 Locking screw of the cover Figure 4 2 Single chamber housing 1 Clamp 2 Locking screw of the cover Figure 4 3 Doub...

Страница 22: ...0 VGK5 6 D A W V R H 1 7 S T U the USB connection for service purposes or parameterisation may only be connected if there is no explosive atmosphere present 4 7 Removal and replacement of the red thre...

Страница 23: ...rning label indicates danger DANGER In case of instrument versions with electrostatically chargeable plastic parts the danger of electrostatic charging and discharging must be taken into account DANGE...

Страница 24: ...solutions Engineering commissioning calibration maintenance and training services Head Office KROHNE Messtechnik GmbH Ludwig Krohne Str 5 47058 Duisburg Germany Tel 49 203 301 0 Fax 49 203 301 10389...

Отзывы: