2.7.5 With separate cable outlet
The intrinsically safe circuits are galvanically isolated from parts which can be grounded.
The metallic parts of OPTIBAR * 5060 VGK5/6/D*A/W/V C/U/0/H/T are electrically connected with
the ground terminals.
For applications requiring equipment category 1G or 1/2G, the intrinsically safe supply and
signal circuits must correspond to protection level ia.
For applications that require equipment category 1G or 1/2G, it is preferable to connect the
OPTIBAR * 5060 VGK5/6/D*A/W/V C/U/0/H/T to appropriate equipment with galvanically isolated,
intrinsically safe circuits.
OPTIBAR * 5060 VGK5/6/D*A/W/V C/U/0/H/T version with separate cable outlet
Circuit between probe unit and
external electronics (terminal 1 - yellow,
terminal 2 - white, terminal 3 - red,
terminal 4 - black)
In protection type intrinsic safety Ex ia IIC
For the OPTIBAR * 5060 VGK5/6/D*A/W/V C/U/0/H/T in the
version with the permanently mounted cable to the probe unit
and external electronics, the length of the supplied cable
between the external housing and the probe unit should not
exceed 180 m.
Table 2-19: OPTIBAR * 5060 version with separate cable