background image

KRIWAN Industrie-Elektronik GmbH · Allmand 11 · D-74670 Forchtenberg · phone (+49) 7947 822 0 · fax (+49) 7947 1288 · e-mail: [email protected] · home: www.kriwan.com

Technical changes reserved

Pr

oduct gr

oup S

Edition: 710.00566.0

INT280-60

®

INT280-60

®

Technical specifications

Order data

Supply voltage
- 52 S 581 S026

AC 50/60Hz 230V ±10% 25VA

- 31 S 581 S026

AC 50/60Hz 24V ±10% 25VA

Permissible ambient temperature 
T

A

-30...+60°C

Permitted rel. humidity

10-95% r. h. no condensation

Medium temperature

-30...+100°C

Operating pressure

-1...+60bar

Test pressure

90bar

Differential pressure

1-25bar

Relay
- Contact

AC 240V 2.5A C300 
at least AC/DC 24V 20mA

- Mechanical service life

Approx. 1 million switching cycles

Protection class acc. to EN 60529 IP65
Supply
- electrical

Push-in spring terminals
0.25-0.75mm

² 

- Oil

7/16"-20 UNF

Mounting

Flange (3-/4-hole)

Housing material

Aluminium
PA glass-fibre-reinforced

Flow rate through valve

1l/min (water 20°C, 1bar 
differential pressure)

Permitted oils

Mineral and ester oils without 
additives

Permitted refrigerants

Non-corrosive, non-flammable

Mounting position

Horizontal (rotatable by 180°), ±2°

Dimensions

See dimensions in mm

Weight

Approx. 1300g

Check base

EN 61000-6-2, EN 61000-6-3
EN 61010-1
Overvoltage category II
Pollution level 2

For additional technical details, see table of parameters

INT280-60 (AC 24V)

31 S 581 S026

INT280-60 (AC 230V)

52 S 581 S026

Accessories and application 
information

see www.kriwan.com

Table of parameters

Parameter name

Unit

Default

Filling cycle type

Fixed

Filling time

s

10

Break time

%

20

Overfill time

s

0

Oil deficiency alarm delay

s

120

Soiling stage 2

Warning

Содержание INT280-60

Страница 1: ...This minimizes the risk of operating without enough oil in the compressor Functional description If the oil level is too low the intelligent filling algorithm controls the oil refill To do this the integrated solenoid valve is opened cyclically The oil level regulator switches the compressor off through the internal relay if the oil level remains too low after an extended period of time Oil refill...

Страница 2: ...lations have to be observed Connection lines that extend from the terminal box have to feature at least a basic insulation The user has to ensure that the connections are properly tight The electrical connection needs to be carried out according to the wiring diagram Prior to installation ensure that the pressure in the refrigeration circuit is and stays equal to the atmospheric pressure The volta...

Страница 3: ...o EN 60529 IP65 Supply electrical Push in spring terminals 0 25 0 75mm Oil 7 16 20 UNF Mounting Flange 3 4 hole Housing material Aluminium PA glass fibre reinforced Flow rate through valve 1l min water 20 C 1bar differential pressure Permitted oils Mineral and ester oils without additives Permitted refrigerants Non corrosive non flammable Mounting position Horizontal rotatable by 180 2 Dimensions ...

Страница 4: ...WAN Industrie Elektronik GmbH Allmand 11 D 74670 Forchtenberg phone 49 7947 822 0 fax 49 7947 1288 e mail info kriwan com home www kriwan com Technical changes reserved Product group S Edition 710 00566 0 ...

Отзывы: