7
KraftPowercon Sweden AB, Hjalmar Petris väg 49, 352 46 Växjö, Sweden, Tel: 0470-705200, Fax: 0470-705201,
www.kraftpowercon.com
3
TECHNICAL DATA
3.1
ELECTRICAL DATA
3.1.1
Range
PRX can be equipped with one or two rectifier modules.
PRX
Likriktarmodul
Model
designation
U
NOM
I
RATED
Mains
power
*1
Mains
current
*1
Mains
fuse
*2
Power
loss
*3
Number
of
modules
I
RATED
Model
designation
(V
DC
)
(A)
(VA)
(A
RMS
)
(A)
(W)
(A)
PRX 24/36
24
36
1150
6
10
160
1
36
PCS 24/36
PRX 24/2x36
72
2300
12
16
310
2
36
PCS 24/36
PRX 24/70
70
2200
12
16
185
1
70
PCS 24/70
PRX 48/18
48
18
1150
6
10
145
1
18
PCS 48/18
PRX 48/2x18
36
2300
12
16
280
2
18
PCS 48/18
PRX 48/50
50
2900
15
20
220
1
50
PCS 48/50
PRX 110/8
110
8
1150
6
10
145
1
8
PCS 110/8
PRX 110/2x8
16
2300
12
16
280
2
8
PCS 110/8
PRX 110/16
16
2200
12
16
170
1
16
PCS 110/16
PRX 110/2x16
32
4400
23
25
330
2
16
PCS 110/16
PRX 110/22
22
2900
15
20
210
1
22
PCS 110/22
PRX 110/2x22
44
5800
30
35
410
2
22
PCS 110/22
PRX 220/10
220
10
2700
14
16
210
1
10
PCS 220/10
PRX 220/2x10
20
5400
28
35
410
2
10
PCS 220/10
*1
: max at 195 V
AC
*2
: recommended value
*3
: type at 230 VAC and full load. Also includes monitoring unit.
3.1.2
Common electrical input data
Rated voltage ............................................... 120
*1
/127
*1
/220/230/240 V
AC
1- phase
Frequency ..................................................... 50 – 60 Hz
Power factor ................................................. > 0.99 at 230 V
AC
, full load
Connection screw terminal block .............. 0.5 – 10 mm
2
*1
: Power derating below 190 V
AC
.
3.1.3
Common electrical output data
Voltage regulation (static) .......................... <±0.5% of nominal output voltage
Voltage regulation (dynamic) .................... <±1% within 3 seconds, 0-100 / 100-10 % load change
Current regulation....................................... <±1% of rated current
Setting range, current limit ........................ 0 - 100% of rated current
Ripple voltage .............................................. <0.1 %
RMS
Ripple current .............................................. <0.1 % of rated current
Efficiency, typical ........................................ up to 92 % at 230 V
AC
Connection screw terminal block .............. 1.5 - 35 mm
2