SM/SV-Space Master Unit Coolers (E316008_B)
8
Table 2 CHECK VALVES KITS
Model
(K) KGG, (P) KGE Suct line Gas inlet Gas relief
(G) HGG, (H) HGE
Gas inlet
SM
Check Valves Kit CV diam CV diam CV diam
Check Valves Kit
CV diam
384
CE269377
1.625
0.500
0.500
CE269381
0.500
426
1.625
0.500
0.500
0.500
440
1.625
0.500
0.500
0.500
501
CE269378
2.125
0.875
0.875
CE269382
0.875
556
2.125
0.875
0.875
0.875
574
2.125
0.875
0.875
0.875
759
2.125
0.875
0.875
0.875
842
2.125
0.875
0.875
0.875
869
2.125
0.875
0.875
0.875
989
CE269379
2.625
0.875
0.875
CE269382
0.875
1070
2.625
0.875
0.875
0.875
1097
2.625
0.875
0.875
0.875
1132
2.625
0.875
0.875
0.875
1186
2.625
0.875
0.875
0.875
1225
CE269380
2.625
1.125
1.125
CE269383
1.125
1393
2.625
1.125
1.125
1.125
1544
2.625
1.125
1.125
1.125
1594
2.625
1.125
1.125
1.125
1465
2 CE269378
2.125
0.875
0.875
2 CE269382
0.875
1523
2.125
0.875
0.875
0.875
1754
2.125
0.875
0.875
0.875
1769
2.125
0.875
0.875
0.875
1985
2 CE269379
2.625
0.875
0.875
0.875
2307
2.625
0.875
0.875
0.875
6.5 REFRIGERANT DISTRIBUTOR NOZZLES
Direct expansion unit coolers are piped using a refrigerant distributor with a
changeable nozzle
design to
equally distribute refrigerant to each circuit of the evaporator coil. Distributor nozzles are installed at the
factory.
The nozzles provided with the unit have been selected for design conditions of 9 F to 11 F T.D. and 90 F (85 F
electric and hot gas defrost) liquid refrigerant at the expansion valve inlet. If the unit will be operated at
conditions that are substantially different from these conditions it may be necessary to select a different size
nozzle. Contact the factory for advice.
The nozzle must be installed in the distributor or the auxiliary side connector before installing the expansion
valve. There are nozzle identification numbers stamped on one side of the nozzle. Be sure to insert the nozzle
into the distributor with these numbers visible in case identification is required later. The nozzle is held in place
by a retainer ring that is easily inserted or removed with a pair of needle nose pliers.