13
KPS-DT30 • Voltage tester
ENG
5. Testing an electricity conductor
circuit
(continuity test).
The continuity test must not be carried out on
active equipment and, where necessary, the
condensers must be discharged. The necessary
voltage for the test is supplied by the voltage
power source integrated into the test handle (A).
Testing is possible within the scale of 0 to 1 M Ω.
Connect the electrodes on the test handles (A)
and (B) to the installation to be tested.
Hold onto test electrodes (A) and (B).
By connecting the test electrodes (1) to an elec-
tricity conductor circuit, the LED (8) will light up.
Testing continuity and reverse direction on
semi-conductors.
The test depending on polarity must not be car-
ried out on active equipment.
The necessary voltage for the test is supplied by
the voltage power source integrated into the test
handle (A). Test handle (A) is the positive pole.
Testing is possible within the scale of 0 to 1 MΩ.
Connect the electrodes on the test handles (A)
and (B) to the installation to be tested.
Hold onto test electrodes (A) and (B).
By connecting the test electrodes (1) to an elec-
tricity conductor circuit, the LED (8) will light up if
the circuit is closed. In the event of reverse direc-
tion, no indication will be given.
6. Testing the earth leak circuit breaker.
The voltage tester can only be used within the
nominal voltage scale from 12 to 690 V.
Never connect the voltage tester to voltage for
more than 30 seconds (Maximum connection
period allowed = 30 s.). Connect the electrodes
(1) on test handles (A) and (B) to the active line
and the earth line of the power supply controlled
by the earth leak circuit breaker to be tested.
Press the button (3) to make the test. Never
keep the button pressed down for more than 2
seconds.
If the earth leak circuit breaker acts, the supply
system is protected against earth leaks. If it does
not act, the earth leak circuit breaker is defective
or there is no circuit breaker installed.
7. Technical information.
Nominal voltage scale: 12 to 690 V AC/DC.
Internal resistance: 20 KΩ.
Screen levels: LED ± 12V, 50V, 120V, 230V,
400V and 690V ~.
Maximum current input level: Is = 52 mA.
Continuity test no-load voltage: maximum 5 V.
Test current: maximum 5 µA.
Nominal frequency scale: 0 < f < 500 Hz.
Maximum on time allowed: 30 seconds.
Operating temperature: -10º C to 50º C.
Protection: IP 54, DIN 400500.
Weight: 183 gr.
Connection cable: 920 mm in length.
Earth leak test current: 32 mA.
Indicator with LED.