3. Installation and repair should be done by a qualified service person. The  room

heater should be inspected before use and at least annually by a professional
service person. More frequent cleaning may be required due to excessive lint from
carpeting and other materials. It is imperative that the control compartments,
burners and circulating air passageways of the heater be kept clean.

CONNECTING TO GAS SUPPLY :

WARNING : Never connect an unregulated gas line to the heater.

An installer supplied, design certified gas pressure regulator must be installed to
bring the gas supply pressure down to 14 inches of water column.

IMPORTANT : Check gas line pressure before connecting heater to gas line.
Gas line pressure must not be higher  than 14 inches of water. If gas line pressure is
higher, heater gas pressure regulator damage could occur.

CAUTION : Use only new, black iron  or steel pipe and internally-tinned copper 
tubing may be used in certain areas. Check your  local codes. Use pipe of large
enough diameter to allow proper gas volume to heater. If pipe is too small, undue
pressure loss will occur.

Typical Gas Supply Pipe Diameters

30,000 BTU/HR Model   3/8" or greater

CAUTION:

Use pipe joint sealant that is resistant to liquefied petroleum gases.

Install sediment trap in supply line as shown in Figure 8 Gas Connection. Locate
sediment trap where it is within reach for cleaning. Locate sediment trap where
trapped matter is not likely to freeze. A sediment trap traps moisture and
contaminants. This keeps them from going into heater controls. If sediment trap
is not installed or is installed wrong, heater may not run properly.

Figure 7

Horizontal

Slots

Mounting

Bracket

(attached to wall)

Stand - Out Tab

Содержание 602-30

Страница 1: ...ppliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s pho...

Страница 2: ...structions Product Identification Local Codes National Fuel Code Unpacking the Heater Package Product Features Fresh Air for Combustion and Ventilation Installation Gas Requirements Leak Checking Log...

Страница 3: ...ocated so that you know where to shut off the gas to the heater If you smell gas your installer has not done a proper job of checking leaks If the connections are not perfectly seated or tightened you...

Страница 4: ...ter and to replace any part of the control system and any gas control which has been under water Keep appliance area clear and free from combustible materials gasoline and other flammable vapors and l...

Страница 5: ...for proper operation If not poor fuel combustion could result Read the following instructions to insure proper fresh air for this and other fuel burning appliances in your home ADEQUATE COMBUSTION VE...

Страница 6: ...LP Propane and make sure the marking on the appliance rating plate agrees with that of the supply gas The rating plate is located on the side of the heater which indicates the type of gas that heater...

Страница 7: ...ther gases CAUTION If you install the heater in a home garage Heater must be at least 18 inches above floor Locate heater where moving vehicle will not hit it Preparing For Installation Select a locat...

Страница 8: ...o wall as shown in Fig 4 4 Insert mounting screws through each bracket and into wall anchors 5 Tighten screws until mounting bracket is firmly fastened to wall Installing Bottom Mounting Screws 1 Loca...

Страница 9: ...Mounted With Base Provided Rear 0 Inches Sides 13 Inches Top 36 Inches Floor 7 Inches NOTICE Maintain the minimum clearances shown in Figure 1 but you can provide greater clearances from floor ceilin...

Страница 10: ...of water If gas line pressure is higher heater gas pressure regulator damage could occur CAUTION Use only new black iron or steel pipe and internally tinned copper tubing may be used in certain areas...

Страница 11: ...LP units check with a full cylinder CAUTION NEVER LEAK TEST WITH AN OPEN FLAME PRESSURE TESTING GAS SUPPLY PIPING SYSTEM The appliance and its individual shutoff valve must be disconnected from the g...

Страница 12: ...consistent good performance without flame impingement on the log Follow the following steps for proper log placement 1 Remove lower panel screen guard and the packaged ceramic log as shown below 2 Re...

Страница 13: ...and safety valve the burner must be lit See operating Instructions Check the rest of the connections for leaks 7 Turn off the heater See Instructions NOTE Never use an open flame to check for a leak A...

Страница 14: ...urn clockwise to the OFF position 4 Wait five minutes to clear any gas Then smell for gas including near the floor If you smell gas follow the safety information on the front page If you don t smell g...

Страница 15: ...the OFF position Shutting Off Burner Only Pilot stays lit Turn control knob clockwise to the PILOT position THERMOSTAT CONTROL OPERATION The thermostat used on these models differs from standard therm...

Страница 16: ...sed in for 30 seconds after lighting pilot After 30 seconds release control knob 6 Replace lower front panel INSPECTING MAIN BURNER AND PILOT BURNER Pilot Flame Pattern The following figures show a co...

Страница 17: ...the exterior with soft bristle brush vacuum cleaner pressurized air Never use a wooden toothpick as it may break off and clog the ODS pilot or main burner port Use a flashlight to inspect the main bur...

Страница 18: ...ple Problem could be result of one or both of the following Partially clogged ODS pilot orifice Low gas pressure 4 Thermocouple damaged 5 Thermocouple connection loose at gas control valve 6 Gas contr...

Страница 19: ...matter in gas or on burner ports 2 Heater burning vapors from paint impurities in air 3 Gas leaks See front page Warnings 1 Not enough fresh air is available 2 Low gas pressure 3 ODS pilot partially...

Страница 20: ...DO NOT USE THIS HEATER AT AN ELEVATION ABOVE 4 500 FEET NOTE For altitudes above 2 000 feet reduce the input rating BTU HR 4 for each 1 000 feet above sea level SPECIFICATIONS MODELS KLH 601 602 601...

Страница 21: ...Page 21 PARTS LIST...

Страница 22: ...t Main Nozzle O D S Pilot Tubing 3 16 Assembly O D S Pilot Assembly Daemyeong Korea Electrode Thermocouple Connector A Connector B Connector C Wall Mounting Bracket L R Wall Mounting Screw Regulator F...

Страница 23: ...PARTICULAR PURPOSE THE REMEDY PROVIDED IN THIS WARRANTY IS EXCLUSIVE AND IS GRANTED IN LIEU OF ALL OTHER REMEDIES IN NO EVENT WILL WORLD MARKETING OF AMERICA BE LIABLE FOR INCIDENTAL OR CONSEQUENTIAL...

Страница 24: ...if one brick is not as bright as another your heater is probably due for a good cleaning Replacement of the thermocouple or pilot assembly is generally not needed Review Heater Maintenance on page 15...

Отзывы: