#BAY-41-MV R.1 July 2021
Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces
FACING AND FINISHING
21
Figure 4.1, Mantel and Trim Requirements
10” (254mm)
8” (203mm)
6” (152mm)
13”
(329mm)
11”
(279mm) 9”
(229mm)
3/4” (19mm)
5
½
”
(139mm)
34
½
”
(877mm)
48”*
(1219mm)
54”**
(1372mm)
58”***
(1473mm)
NON-COMBUSTIBLE ZONE
COMBUSTIBLE FLOOR
1/2” (13mm)
NON-COMBUSTIBLE
MATERIAL ONLY
*NON-COMBUSTIBLE ZONE: 48” (1219mm) minimum chamber height when venting from rear vent exits
**NON-COMBUSTIBLE ZONE: 54” (1372mm) minimum chamber height for Natural Gas & Propane top vent minimum horizontal vent terminations using rigid pipe
***NON-COMBUSTIBLE ZONE: 58” (1473mm) minimum chamber height for top vent minimum horizontal vent terminations using flex pipe
Nominal 2” x 4” framing used in enclosure framing