4

Failure modes of PSK.P4 front panel.

Simultaneous  blinking  of  all    indicators  means  that  one  (or  both)  temperature  sensors  failed  or  are  disconnected. 
By  using  the  right  arrow  the  one  could  review  the  return  or  flow temperature. If the main indicator shows E replace the
adequate temperature sensor. In case of return temperature sensor failure the boiler will run in the failure mode and the  
heating temperature will be computed by using difference between main temperature settings and the supply temperature. 
Detection of the supply temperature sensor failure blocks the heating of the boiler.

2.  Control panel settings

PSK.P4 front panel service mode configuration.

To set the service modes turn off the boiler by pressing and holding the power

 button. Then press and hold the right 

arrow button and simultaneously press the power button. Use the upper and lower arrow buttons to change the parameter 
value or mode. Use the right arrow button to move to the next parameter.

Parameter

Display 

Description

Circulating pump mode

PA

Automatic mode

Pr

Continuous working mode 

Power board

G1 ÷ G6

Number of supplying heating elements 

Temperature ranges

Po

Floor heating type 30-60°C

(with no possibility to heat the DHWT)

no

Standard type 40-85°C

Three phase mains supply  

symmetry 

3F

No symmetry detection

3F.

Symmetry detection is active. The K indicator is ON. The boiler stops heating the system if phase is missing

Cascade mode

r0

Separate standard mode

r1

Cascade working mode

Boiler identification number

A1 ÷ A8

Set the A number exclusively to identify each boiler.

Position A1 boiler no 1 ... A8 boiler no 8

DHWT loading temperature value

0

Heating of the DHWT is blocked.

The DHWT indicator is off.

50 ÷ 85

DHWT temperature range.

The DHWT indicator is on.

Power of the heating box

1 - 36, indicator 

'kW' lits

Set the proper number according to the power of the heating box 

and the number of active heating elements

All the settings are stored automatically. After settings are changed  turn off device by pressing and holding the power button
for 3 sec. Then turn the boiler on again. The boiler will work with the new settings.

Table 1.

Содержание EKCO.L1 p

Страница 1: ...1 KOSPEL S A KOSZALIN ul Olchowa 1 SERVICE MANUAL EKCO L1 z EKCO L1N z EKCO L1 p EKCO L1N p EKCO36 L1 EKCO36 L1N 01 16 06 2010...

Страница 2: ...0 Pic 6 Power board 10 8 DHWT connection chart 11 Pic 7 Example of three way valve connection 11 9 Cascade unit for a heating system with two or more heating boilers 12 Pic 8 Cascade heating system fo...

Страница 3: ...3 1 Front view Pic 1a EKCO L1 z EKCO L1 p EKCO36 L1 Pic 1b EKCO L1N z EKCO L1N p EKCO36 L1N...

Страница 4: ...o the next parameter Parameter Display Description Circulating pump mode PA Automatic mode Pr Continuous working mode Power board G1 G6 Number of supplying heating elements Temperature ranges Po Floor...

Страница 5: ...odule socket IN OUT A heat exchanger indicator B pump and ow indicator C heating on and room thermostat indicator D inlet temperature indicator E outlet temperature indicator F medium temperature sett...

Страница 6: ...emperature sensor DS 1820 WZ DHWT thermostat RP jumper or room thermostat NA jumper or superior device ZAS three way valve ZM power module ribbon cable I2C PSK P4 cable ribbon cable 5 pin X NA PSK P4...

Страница 7: ...ting box failure Change the heating box The A indicator is on The boiler is heating only central heating The three way valve failure Check the servo Replace the servo of valve ZIO 21 failure Replace Z...

Страница 8: ...able page 18 41 00272 16 Table page 18 45 00115 42 00373 41 00272 41 00272 3 00863 45 00115 23 00144 21 Table page 18 25 00035 27 Table page 18 44 00647 42 00373 29 00492 42 00373 17 Table page 10 42...

Страница 9: ...iler EKCO L1Nz EKCO L1Np EKCO36 L1N 28 00853 22 Table page 18 21 Table page 18 12 00784 10 01252 41 00272 41 00272 42 00373 42 00373 42 00373 9 01251 Note Only parts that di ers from EKCO L1 are shown...

Страница 10: ...01160 ver 30 6 33 16 35 08 11 40 12 06 EKCO36 L1 36 00903 ver 36 6 28 16 32 84 12 18 14 20 EKCO L1F 4 01027 ver 12 6 68 08 75 24 2 90 3 30 220V EKCO L1F 6 01029 ver 18 6 44 50 49 18 4 40 5 00 EKCO L1...

Страница 11: ...oltage connecton to black wire will open A B to B way The A B A and B indicates appropriate ends of the valve Pic 7 An example of three way valve and temperature sensor connections to ZIO 21 board If...

Страница 12: ...Pictures below show some examples of cascade systems connections 9 Cascade unit for a heating system with two or more heating boilers Pic 8 Direct supply boilers heating system and the DHW tank The wi...

Страница 13: ...f all the slave boilers PSK P4 The master control panel controls all the slave boilers panels therefore temperature settings cannot be changed individually on PSK P4 panel Each of the slave boilers ca...

Страница 14: ...kW 30kW 36kW E1 heating box M1 Circulating pump F1 WT 3 safety cut off A1 Front panel BV ow sensor A2 Power board T1 inlet temperature sensor K Capillary WT 3 T2 inlet temperature sensor A3 ZIO 21 boa...

Страница 15: ...box M1 Circulating pump F1 WT 3 safety cut off A1 Front panel BV ow sensor A2 Power board T1 inlet temperature sensor K Capillary WT 3 T2 inlet temperature sensor A3 ZIO 21 board superordi nated signa...

Страница 16: ...heating box M1 Circulating pump F1 WT 3 safety cut off A1 Front panel BV ow sensor A2 Power board T1 inlet temperature sensor K Capillary WT 3 T2 inlet temperature sensor A3 ZIO 21 board superordi na...

Страница 17: ...Or jumper Or jumper yelow N blue LA brown LB black blue blue red red G6 G4 G2 G5 G3 U V W ZM 43 NA Tin Tout Q I2C PSK P4 Three way valve servo Heating box A B A B Thermostat or NO NO NC B A Parallel...

Страница 18: ...nection pipe 1 1 01158 EKCO36 L1 09 00 00a Power board connection pipe 1 1 17 00904 EKCO36 L 10 00 00a Power board EKCO L1 type 36kW 1 1 01011 EKCO L 10 00 00a I Power board EKCO L1 type I 12 24 1 1 0...

Страница 19: ...Pump UPSO 15 70 130 9H 1 1 28 00853 Expansion vessel CP387 G1 2 6L 1 1 29 00492 EPCO M 04 00 00 Pump connection pipe 1 1 1 1 30 35 36 37 38 39 40 00253 Gasket 1 5x14 8x8 1 1 1 1 41 00272 Gasket 1 5x1...

Страница 20: ...ent A 17 4 26 0 34 8 25 37 5 50 60 Fuse rated current A 20 32 40 32 50 63 80 Min connecting wires section mm2 3 x 2 5 3 x 4 3 x 6 3 x 2 5 3 x 6 3 x 10 Max connecting wires section mm2 3 x 16 3 x 25 Bo...

Отзывы: