
25
14.1 Pump Wilo Yonos Para
Pic.17. Settings via operating knob
Variable differential pressure
The differential-pressure setpoint H is increased linearly over the permitted volume flow
range between ½H and H. The differential pressure generated by the pump is adjusted to the
corresponding differential-pressure setpoint. This control mode is especially useful in heating
systems with radiators, since the flow noises at the thermostatic valves are reduced.
Constant differential pressure
The differential-pressure setpoint H is kept constant over the permitted volume flow range at
the set differential-pressure setpoint up to the maximum pump curve. Wilo recommends this
control mode for underfloor-heating circuits or older heating systems with large-sized pipes as
well as for all applications with no changeable pipe system curve, e.g. boiler charge pumps.
Venting function
During automatic venting function (10min) the Pump runs alternately with high and low speeds
to help air bubble from the pump to agglomerate and to lead direct to the venting valve of the
installation.
Содержание ECKO.TM
Страница 1: ...1 KOSPEL S A KOSZALIN ul Olchowa 1 SERVICE MANUAL EKCO T ECKO TM 17 11 2020 ...
Страница 5: ...5 Pic 1b EKCO TM boiler 5 01216 19 01220 23 00035 32 6 01217 ...
Страница 6: ...Service manual EKCO T EKCO TM 6 2 Construction of boilers Pic 2a Construction of the boiler EKCO T ...
Страница 7: ...7 Pic 2bConstruction of the boiler EKCO TM ...
Страница 15: ...15 6 Connection of control panel PSK P4 and ZIO 23 board Pic 6 Connection of control panel PSK P4 ...
Страница 17: ...17 8 Connection of control panel PSK M2 and ZIO 24 board Pic 8 ZIO 24 board connection 01 01 2 ...
Страница 19: ...19 10 Connection diagram of heating box Pic 10Connection diagram of heating box ZIO 23 or ZIO 24 ...
Страница 26: ...Service manual EKCO T EKCO TM 26 14 2 Pump Wilo Yonos Para alarm status Tab 7 Alarm status ...