2.

 

Before switching on the main power supply, the AC power should be checked to ensure that the 

supplied voltage fluctuation range does not exceed ±10% of the voltage and frequency indicated by 
the equipment. This check is especially important for voltage fluctuations that can occur in high load 
situations. 

3.

 

The dehumidifier must be grounded and a power disconnect switch set to ensure that the unit is 

powered off during inspection and service. 

4.

 

The  fuse  current  of  the  power  supply  fuse  is  1.5  to  2  times  the  rated  current  of  the  installed 

dehumidifier. The fuse should be installed in the dehumidifier attachment. The power supply cable 
and  main  fuse  are  optional  to  handle  the  correct  operating  power  of  the  dehumidifier.  Fuse  rating: 
10A 250V, 16A 250V. 

5.

 

If the power cord is damaged, it must be replaced by the manufacturer or a professional authorized 

person in order to avoid danger.

 

6.

 

Placing. When the dehumidifier is working, make sure the 

Minimum distance between two machines is 10cm 

Minimum distance between air outlet and the top is 200cm 

Minimum distance between the back and the wall is 20cm 

Содержание KM-480S

Страница 1: ...Industrial Dehumidifier User Manual KM 480S www kosmen vn...

Страница 2: ...1 2 Function of the Button 2 2 1 Operation 2 2 2 Features 4 3 Operating Instructions 4 3 1 Dehumidifying Running 4 3 2 Drain Indicator 5 4 Device Installation 5 5 Specification 7 6 Error Code Explana...

Страница 3: ...b o quan tr ng 09 2 C c n t ch c n ng 10 2 1 V n h nh 10 2 2 Ch c n ng 12 3 H ng d n v n h nh 12 3 1 Ch y m y h t m 12 3 2 n b o tho t n c 13 4 C i t thi t b 14 5 Th ng s k thu t 15 6 Gi i th ch m l i...

Страница 4: ...ke sure that it is not punctured or frayed Inspect the plug to ensure that the prongs are secure and the plastic surrounding it is not cracked Do not suddenly unplug the power plug while the machine i...

Страница 5: ...2 2 Function of the Button 2 1 Operation...

Страница 6: ...3...

Страница 7: ...l operating range 10 90 6 If the dehumidifier is not used for a long time remove the power cord or power off 7 The function of the memory system the function can function before the power is turned of...

Страница 8: ...the pipe from being too long or the pressure is formed in the pipe when the water outlet is blocked The water flow is not smooth resulting in water leakage Inspection and Maintenance Parts 1 3 months...

Страница 9: ...fuse current of the power supply fuse is 1 5 to 2 times the rated current of the installed dehumidifier The fuse should be installed in the dehumidifier attachment The power supply cable and main fus...

Страница 10: ...Drainage Dimensions 1030 510 1815 mm Net Weight 182 KGS 6 Error Code Explanation Fault Code The failure How to do with it E1 Temperature sensor breakdown To replace with new temperature sensor E2 Humi...

Страница 11: ...iate 2 The front and back may be blocked 3 Dehumidification time isn t enough 4 Door and window may be open 5 Temperature 5 or 38 1 Set appropriate humidity 2 Clear the obstructions 3 Keep waiting 4 C...

Страница 12: ...i m tra d y i n c n th n m b o r ng n kh ng b th ng ho c s n Ki m tra ph ch c m m b o c c u c m c ch c ch n v l p nh a bao quanh kh ng b n t Kh ng c r t ph ch c m i n t ng t khi m y ang v n h nh Tr c...

Страница 13: ...10 2 C c n t ch c n ng 2 1 V n h nh...

Страница 14: ...11...

Страница 15: ...m so t m 10 90 6 N u m y h t m kh ng c s d ng trong m t th i gian d i h y r t d y ngu n ho c t t ngu n 7 H th ng c ch c n ng ghi nh ch c n ng n y c th ho t ng tr c khi t t ngu n trong v ng 72 gi sau...

Страница 16: ...n c tr nh tr ng h p ng ng qu d i ho c t o p l c trong ng khi ng tho t n c b t c D ng n c ch y kh ng th ng su t d n n r r n c Ki m tra v B o tr C c b ph n 1 3 th ng 12 th ng M ng l c V sinh m ng l c M...

Страница 17: ...p v t n s m thi t y u c u Vi c ki m tra n y c bi t quan tr ng i v i c c dao ng i n p c th x y ra trong c c t nh hu ng qu t i 3 M y h t m ph i c n i t v t c ng t c ng t i n m b o thi t b c t t ngu n tr...

Страница 18: ...pply 380V 50Hz Operating Temp 5 38 Water Tank Drainage Dimensions 1030 510 1815 mm Net Weight 182 KGS 6 Gi i th ch m l i M l i L i H ng x l E1 S c c m bi n nhi t Thay c m bi n nhi t m i E2 S c c m bi...

Страница 19: ...u ng h t m kh ng t y u c u 1 C i t m kh ng ph h p 2 M t tr c v m t sau c a m y h t m c th b c n tr 3 Th i gian h t m c th kh ng 4 C a ra v o v c a s ang m 5 Nhi t trong nh th p h n 5 ho c cao h n 38...

Страница 20: ...iep Binh Phuoc Thu Duc City Ho Chi Minh City Vietnam Ha Noi office No 3 Lane 495 Nguyen Trai Thanh Xuan Nam Ward Thanh Xuan District Ha Noi City Vietnam Da Nang office No 385B Hai Phong Tan Chinh Ward...

Отзывы: