Electrical Control System
1.3.9 Follow me(Optional)
1) If the indoor PCB receives the signal which results from pressing the FOLLOW ME button on remote
controller, the buzzer will emit a sound and this indicates the follow me function is initiated. But when the
indoor PCB receives signal which sent from remote controller every 3 minutes, the buzzer will not
respond. When the unit is running with follow-me function, the PCB will control the unit according to the
temperature from follow-me signal, and the temperature collection function of room temperature sensor
will be shielded.
2) When the follow-me function is available, the PCB will not respond according to the setting temperature
from follow-me signal every 3 minutes.
3) The PCB will take action to the mode change information from remote controller signal, and the
follow-me function will be turned off. (if the wired remote controller does not initiate follow me function).
4) When the unit is running with follow-me function, if the PCB doesn’t receive any signal from remote
controller for 7 minutes or pressing FOLLOW ME button again, the follow-me function will be turned off
automatically, and the temperature collection function of room temperature sensor will be available, the
PCB will control the unit according to the room temperature detected from its own room temperature
sensor and setting temperature.
5)
When the indoor PCB receives the follow-me signal from wired remote controller, the control is the
same as that from wireless remote controller, but buzzer will not respond. When the PCB receives
turning-off follow-me signal from wired remote controller, the unit will quit follow-me function at once.
The follow-me function controlled by wired remote controller prevails that by wireless remote controller.
1.3.10 Point Check Function
There is a check switch in outdoor PCB.
Press the switch SW1 to check the states of unit when the unit is running.
Press the switch N times it will display the content corresponding to No. N. After getting into the check
function, it will display No. N with 1.5s, meanwhile the low bit decimal of digit display flashing, indicated to
get into the check function display. After 1.5s, it will display the content corresponding to No. N.
the digital display tube will display the follow procedure when push SW1 each time.
N Display
Remark
00
Normal display
Display running frequency, running state or malfunction code
01
Indoor unit capacity demand code
Actual data*HP*10
If capacity demand code is higher than 99, the digital display
tube will show single digit and tens digit. (For example, the
digital display tube show “5.0”,it means the capacity demand
is 15. the digital display tube show “60”,it means the capacity
demand is 6.0)
02
Amendatory capacity demand code
03
The frequency after the capacity requirement
transfer
Содержание KV24 ODU-ARF21C
Страница 1: ......
Страница 6: ...Nomenclature 4 General Information 3 Nomenclature 3 1 Indoor Outdoor Unit...
Страница 11: ...Features Indoor Units 9 Alarm lamp Long distance on off controller...
Страница 13: ...Service Space Indoor Units 11 3 Service Space 1000mm 1000mm 1000mm 1000m m...
Страница 14: ...Wiring diagrams 12 Indoor Units 4 Wiring diagrams KV24CC ARF21C KV36CC ARF21C KV48CC ARF21C KV60CC ARF21C...
Страница 19: ...Field Wiring Indoor Units 17 9 Field Wiring 24K 36K...
Страница 20: ...Field Wiring 18 Indoor Units 48K 60K...
Страница 27: ...Wiring Diagrams Indoor Units 25 4 Wiring Diagrams KV24DH ARF21C KV36DH ARF21C KV48DH ARF21C KV60DH ARF21C...
Страница 34: ...Field Wiring 32 Indoor Units 10 Field Wiring 24K 36K...
Страница 35: ...Field Wiring Indoor Units 33 48K 60K...
Страница 39: ...Service Space Indoor Units 37 3 Service Space...
Страница 40: ...Wiring Diagrams 38 Indoor Units 4 Wiring Diagrams KV24CM ARF21C KV36CM ARF21C KV48CM ARF21C KV60CM ARF21C...
Страница 44: ...Ceiling Floor Type 42 Ceiling Floor Type 9 Field Wiring 24K 36K...
Страница 45: ...Ceiling Floor Type Ceiling Floor Type 43 48K 60K...
Страница 48: ...Dimensions 46 Floor standing Type 2 Dimensions Dimension Mode W mm D mm H mm 36k 550 350 1800 60k 610 390 1925...
Страница 49: ...Service Space Floor standing Type 47 3 Service Space...
Страница 50: ...Wiring Diagrams 48 Floor standing Type 4 Wiring Diagrams KV36FM ARF21C KV60FM ARF21C...
Страница 55: ...Field Wiring Floor standing Type 53 9 Field Wiring 36K...
Страница 56: ...Field Wiring 54 Floor standing Type 60K...
Страница 59: ...Dimensions Outdoor Units 57 Model KBtu h Unit mm W D H W1 A B 48 60 952 415 1333 1045 634 404...
Страница 62: ...Wiring Diagrams 60 Outdoor Units 4 Wiring Diagrams KV24ODU ARF21C KV36ODU ARF21C...
Страница 63: ...Wiring Diagrams Outdoor Units 61 KV48ODU ARF21C KV60ODU CRF21C...
Страница 101: ...Electrical Control Function Electrical Control System 99 Shutdown stop 49 Electrical disconnect 50 DR stop 51...
Страница 103: ...Troubleshooting Electrical Control System 101 2 1 5 Display board of floor standing...
Страница 113: ...Troubleshooting Electrical Control System 111 2 4 4 2 E1 malfunction For 485 communication E1...
Страница 114: ...Troubleshooting 112 Electrical Control System 2 4 4 3 J4 malfunction J4...
Страница 116: ...Troubleshooting 114 Electrical Control System 2 4 4 5 P6 malfunction P6...
Страница 117: ...Troubleshooting Electrical Control System 115 2 4 4 6 J5 malfunction J5...
Страница 119: ...Troubleshooting Electrical Control System 117 2 4 4 8 F0 malfunction F0...
Страница 123: ...Troubleshooting Electrical Control System 121 2 4 4 12 J0 malfunction J0...