Instruction Manual PERCEDOS

®

Temperature monitoring:

In  order  to  ensure  safe  charging  of  the  electrical  vehicle  at  all  times,  the  

PERCEDOS

®

  has  internal  temperature  monitoring  and  temperature-related 

charging current optimization. This ensures that the permissible charging cur-

rent is set automatically with consideration for safety aspects. This guarantees 

safe, unsupervised operation with optimized charging times.

Charging current optimization by means of internal temperature monitoring:

•  The temperature monitoring is switched on automatically, as soon as the 

charging of the vehicle battery begins.

•  As soon as the temperature sensor measures an excessive temperature, 

the preset charging current is automatically reduced by one charging level 
(e.g. from 16A to 13A). 

•  In case of temperature reduction, the charging current is automatically 

increased by one charging level up to the maximum possible charging 
current (e.g. from 13A to 16A).

•  The charging procedure is permanently switched off if the excessive tempe-

rature continues to be measured when the lowest charging level of 6A is 
reached.

Display PERCEDOS

®

 illuminates red. 

Display vehicle and current indicators are off.

Switch-off in case of critical temperature:

•  If a critical temperature occurs, the charging procedure is immediately 

permanently switched off.

Display PERCEDOS

®

 illuminates red. 

Display vehicle and current indicators are off.

Reset of temperature monitoring:

•  If the charging procedure has been permanently switched off automatically 

by the temperature monitoring, this must be manually reset after elimina-
ting the fault.

For this, proceed as follows:
•  Switch the operating status of the PERCEDOS

®

 from active to inactive.

•  This resets the temperature monitoring.

Display PERCEDOS

®

 blinks green.

•  If the charging procedure is to be continued, switch the operating status of 

the PERCEDOS

®

 from inactive to active.

Display PERCEDOS

®

 illuminates green.

Recommendation:

•  Only reset temperature monitoring if the cause of the excessive tempera-

ture has been eliminated and the device has first been tested for proper 
function, e.g. testing by an electrician.

 

Содержание PERCEDOS

Страница 1: ...PERCEDOS by PERCEDOS by Instruction Manual Technical Information...

Страница 2: ...d wire and its freedom from faults So that the PERCEDOS can detect external voltage on the protective ground the device must be connected to the electrical vehicle The function external voltage detect...

Страница 3: ...otective ground wire is activated PERCEDOS only attached to the vehicle Device is not being supplied with mains voltage device off No visual feedback possible No protective ground monitoring possible...

Страница 4: ...reen Battery charging procedure Only possible if the PERCEDOS has not detected any fault and is acti vated Standby Vehicle connection has been detected Charging procedure possible but not yet switched...

Страница 5: ...splay PERCEDOS blinks green Then press button 0 and button I simultaneously and keep pressed for approx 5 seconds During initial parameterization delivered status all of the LED s of the current indic...

Страница 6: ...ing procedure is permanently switched off if the excessive tempe rature continues to be measured when the lowest charging level of 6A is reached Display PERCEDOS illuminates red Display vehicle and cu...

Страница 7: ...allo wed after it is switched off for the fourth time permanent switch off Display PERCEDOS illuminates red Display vehicle and current indicators are off Manual test of the differential fault current...

Страница 8: ...fault current function and an operating hours meter monitors the maximum recommended operating time until the next retesting Periodic self test The PERCEDOS checks the differential fault current funct...

Страница 9: ...ot switch on charging procedure Have the PERCEDOS checked immediately by an electrician Reset operating hours meter The operating hours meter can be manually reset in inactive operating status For thi...

Страница 10: ...NTC resistance optional External temperature observation NTC resistance in power supply plug Vehicle communication Integrated communication modul PWM according IEC 61851 Data port short circuit proof...

Страница 11: ...green periodic self test has activated Operating hours exceeded Current indicator 1 Displays illuminates when the vehicle is being actively charged Otherwise no display off 2 Illuminates green momenta...

Страница 12: ...l vertrieb kopp euKopp Austria GmbH Theodor Simoneit Stra e 2 A 4160 Aigen Tel 43 7281 6566 0 Fax 43 7281 8790 Technische Beschreibungen Abbildungen und Leistungsangaben stellen keine zugesagten Eigen...

Отзывы: